3192 H4TU-C
CLEI: T1L56YSC_ _
LED STATUS
DSL1/DSL2 ● Green Loop 1/ Loop 2 synchronization achieved and signal is present.
No errors currently detected, and SNR margin ≥ 3 dB.
● Red Loop 1/ Loop 2 synchronization not achieved, in sync with errors,
or SNR margin < 3 dB.
DSX ● Green DSX-1 signal present and no errors currently detected.
● Red In framed mode, denotes loss of framing or loss of sync at the
DSX-1 input. In unframed mode, denotes loss of signal DSX-1
input.
ALM ●● Off No T1 alarms are active.
● Red Loss of DSX-1 signal from the network.
● Yellow Loss of DS1 signal from the CPE.
ESF/SF ●● Off Unit has detected Unframed data.
● Yellow Unit has detected ESF framing data.
● Green Unit has detected SF framing data.
B8ZS/AMI ● Yellow Unit has detected B8ZS line coding data.
● Green Unit has detected AMI line coding data.
LBK ●● Off No local loopbacks active.
● Yellow Local loopback active.
DSX EQ SPLITTING JACKS
TX DSX-1 transmit toward the local loop (intrusive)
RX DSX-1 receive from the local loop (intrusive)
DSX MONITOR JACKS
TX DSX-1 transmit toward the local loop (nonintrusive)
RX DSX-1 receive from the local loop (nonintrusive)
COMPLIANCE
WARNING: Up to –200 VDC might be present on telecommunications wiring. Ensure chassis
ground is properly connected. The DSX-1 interface is intended for connection to
intra-building wiring only.
This product is intended for installation in restricted access locations only and in equipment
with a Type “B” or “E” enclosure.
This product provides span powering voltage (negative only with respect to ground, –190 VDC
nominal, GFI protection < 5 mA) and meets all requirements of Bellcore GR-1089-CORE (Class A2),
and ANSI T1.418-2002. This product is NRTL Listed to the applicable UL standards.
POWERING MODE
The H4TU-C provides –190 VDC span powering voltage and will provide powering to the H4Rs
and the H4TU-R. The –190 VDC span powering voltage is provided on Loop 2.
■ For a complete Installation and Maintenance Practice (P/N 61222404L1-5): 877-457-5007, Faxback Document 885. Please have your fax number ready. ■
OR DECREASE IN RELIABILITY.
HANDLING PRECAUTIONS REQUIRED.
H4TU-C EDGE CONNECTOR WIRING
JOBAID
61222404L1-22D
0311
#61222404L1-22D#
DEFAULT PROVISIONING VALUES
Provisioning Options Option Settings Default Settings
1. DSX-1 Line Build Out 0-133 Feet 0-133 Feet
133-266 Feet
266- 399 Feet
399-533 Feet
533-655 Feet
2. DSX-1/DS1 Line Code AMI, B8ZS B8ZS
3. DSX-1/DS1 Framing SF, ESF, Unframed, Auto ESF
4. Forced Frame Conversion Enabled, Disabled Disabled
5. Smartjack Loopback Enabled, Disabled Enabled
6. Loopback Timeout None, 120 Minutes 120 Minutes
7. Latching Loopback Mode T1 (Disabled), FT1 (Enabled) T1 (Disabled)
8. DS1 TX Level 0 dB, –7.5 dB, –15 dB –7.5 dB
9. Span Power Enabled, Disabled Enabled
10. Customer Loss Indicator AIS, AIS/CI, Loopback AIS/CI
11. PRM Setting None, SPRM, NPRM, Auto Auto
12. Loop Atten Alarm Threshold 0 (Disabled) 34 dB
1-99 dB
13. SNR Margin Alarm Threshold 0 (Disabled) 4 dB
1-15 dB
14. Remote Provisioning Enabled, Disabled Enabled