25
Table 5 – Thermistor Resistance vs Temperature
Values f or Space Temperature Sensor, Supply Air
Temperature Sensor, and Outdoor Air Temperature
Sensor
TEMP
(C)
TEMP
(F)
RESISTANCE
(Ohms)
--- 40 --- 40 335,651
--- 35 --- 31 242,195
--- 30 --- 22 176,683
--- 25 --- 13 130,243
--- 20 --- 4 96,974
--- 15 5 72,895
--- 10 14 55,298
--- 5 23 42,315
0 32 32,651
5 41 25,395
10 50 19,903
15 59 15,714
20 68 12,494
25 77 10,000
30 86 8,056
35 95 6,530
40 104 5,325
45 113 4,367
50 122 3,601
55 131 2,985
60 140 2,487
65 149 2,082
70 158 1,752
NOTE: The sensor must be mounted in the discharge
airstre am downstream of the cooling coil and any heati ng
devic es. Be sure the probe tip does not come in contact
with any of the unit’s heater surfaces.
Outdoor Air Temperature (OAT) Sensor — The OAT is
factory-- mounted in the Economizer 2 (FIOP or
accessory). It is a nominal 10k ohm thermistor attached to
an eyelet mounting ring. See Table 5 for
temperature--resistance characteristic.
Economizer 2 — The PremierLink control is used with
Economizer 2 (option or accessory) for outdoor air
management. The damper position is controlled directly
by the PremierLink control; Economizer 2 has no internal
logic device.
Outdoor air management functions can be enhanced with
field--installation of these accessory control devices:
Enthalpy control (outdoor air or di fferent ial sensors)
Space CO2 sensor
Outdoor air CO2 sensor
Refer to Table 6 for accessory part numbers
Field connections — Field connections for accessory
sensor and input devices are made at the 16--pole terminal
block (TB1) located on the control box bottom shelf in
front of the PremierLi nk control. Some input devices also
require a 24--vac signal source; connect at LCTB terminal
R at “THERMOSTAT” connection strip for this signal
source. See connections figures on following pages for
field connection locations (and for continued connections
at the PremierLink board inputs).
Table 7 provides a summary of field connections for units
equipped with Space Sensor. Table 8 provides a summary
of field connections for units equipped with Space
Thermostat.
Space Sensors -- The PremierLink controller is
factory-- shipped configured for Space Sensor Mode. A
Carrie r T--55 or T--56 space sensor must be used. T--55
space temperature sensor provides a signal of space
temperature to the PremierLink control . T--56 provides
same space temperature signal plus it allows for
adjustment of space temperature setpoints from the face of
the sensor by the occupants. See Table 5 for temperature
versus resistance characteristic on the space sensors.
Connect T--55 -- See Fig. 36 for typical T--55 internal
connec tions. Connect the T--55 SEN termina ls to TB1
terminals 1 and 3 (see Fig. 37).
2
3
45
61
SW1
SEN
BRN (GND)
BLU (SPT)
RED(+)
WHT(GND)
BLK(-)
CCN COM
SENSOR WIRING
C08201
Fig. 36 -- T--55 Space Temperature Sensor Wiring
SEN J6-7
J6-6
1
3
TB1 PL
SEN
C08212
Fig. 37 -- P remierLink T55 Sensor
50TC