A SERVICE OF

logo

Protocol X DCA
Configuration Guide
GE Energy Services
Restricted A197-0CG-1.00-2
Full
21
F005: A197_PAR rec <x> and <y>, Partitions overlap
Cause:
Records <x> and <y> of the A197_PAR are mapped by the same SRU record and have
ranges of addresses that overlap.
Remedy:
Make sure all partitions that are mapped by the same SRU have address ranges that do not
overlap.
F006: A197_COM rec <x>, Only one SRU allowed in Full-Duplex
Cause:
When in Full-Duplex mode, only one SRU should be mapped.
Remedy:
Make sure there is only one SRU mapped for A197_COM records that are configured for
Full-Duplex mode.
F100: Future expansion points not NULLPTR
Cause:
There is an interface error between the DCA and the DCA engine.
The DCA stack is not valid.
Remedy:
Contact the Customer Service Department and report this error.
Reboot the RTU.
F101: Unable to find table <table_name>
Cause:
The DCA was unable to locate one of its required configuration tables.
Remedy:
Ensure the <table_name> table exists and is comprised of at least one record.