Guidelines for the Safety of the User and Protection of the FX
2NC
-4AD
special function block.
This manual should be used by trained and competent personnel. The
definition of such a person or persons is as follows:
a)Any engineer using the product associated with this manual, should be of a
competent nature, trained and qualified to the local and national standards.
These engineers should be fully aware of all aspects of safety with regards
to automated equipment.
b)Any commissioning or service engineer must be of a competent nature,
trained and qualified to the local and national standards.
c) All operators of the completed equipment should be trained to use this
product in a safe and coordinated manner in compliance to established
safety practices.
Note:The term `completed equipment' refers to a third party constructed
device which contains or uses the product associated with this manual.
●
●●
●
Note concerning the CE marking
●
●●
●
CE marking does not guarantee that an entire mechanical module produced
in accordance with the contents of the notification comply with the following
standards. Compliance to EMC standards of the entire mechanical module
should be checked by the user / manufacturer.
Standards with which this product complies
Type : Programmable Controller (Open Type Equipment)
Models : Products manufactured starting April 1st, 2003.
For more details please contact the local Mitsubishi Electric sales site.
- Notes for compliance to EMC regulation.
It is necessary to install the FX
2NC
-4AD in a shielded metal control panel.
For further information manual concerning the FX Series, refer to the following table.
List of Further Information Manuals
1. Introduction
The FX
2NC
-4AD analog input block (hereafter referred to as "FX
2NC
-4AD")
converts 4 points of analog input values (voltage and current inputs) into
digital values, and transfers them to the PLC main unit.
The FX
2NC
-4AD can be connected to the FX
2NC
Series PLC.
1) A combination of voltage and current analog inputs selectable via the PLC
TO instruction should be used to configure the individual input channels.
2) The voltage input range can be selected within -10 to 10V, alternatively, the
current input range can be selected within -20 to 20mA and 4 to 20mA.
The input characteristics can be adjusted for each channel (except when
!
=2, 5, 8 is set in BFM #0 that disables all changes to the offset or gain).
3) The resolution is 0.32 mV (20 V × 1/64,000) or 2.50 mV (20 V × 1/8,000)
when voltage input is used, and 1.25 µA (40 mA × 1/32,000) or 5.00 µA (40
mA × 1/8,000) when current input is used.
4) Data transfer with the PLC is performed via the buffer memories of the
FX
2NC
-4AD using FROM/TO instructions.
Electromagnetic Compatibility
Standards
(EMC)
Remark
EN61000-6-4:2001
Electromagnetic compatibility
-Generic standards - Emission
standard for Industrial environment
Compliance with all relevant aspects
of the standard. (Radiated Emissions
and Mains Terminal Voltage
Emissions)
EN61000-6-2:2001
Electromagnetic compatibility
-Generic standards Immunity for
industrial environments.
Compliance with all relevant aspects
of the standard. (RF immunity, Fast
transients, ESD, Conducted, Surges,
Power magnetic fields, Voltage dips
and Voltage interruptions)
Manual Name Manual No. Description
FX
2NC
Hardware
Manual
JY992D76401
This manual contains hardware explanations
of wiring, installation and specifications for
the FX
2NC
Series programmable controllers.
FX
Programming
Manual II
JY992D88101
This manual contains instruction
explanations for the FX
1S
, FX
1N
, FX
2N
and
FX
2NC
Series programmable controllers.
2. External Dimensions and Part Name
Accessory:Special function block number label, Power crossover cable
FX
2NC
-10BPCB1
1)Status indicator LED 2)Terminal connector (European type)
3),3)’Extension port 4)Slide lock for extension block
5)DIN rail clip 6)Power supply connector (24V DC)
7)Power supply connector (Supply for extension block)
The connector 3)' is equipped with a cover.
- Never wire the terminals.
• Status indicator LED
• Install the FX
2NC
-4AD on the right side of the main unit, extension block or
special function block of the FX
2NC
Series PLC.
• DIN rail installation
The FX
2NC
-4AD can be installed on DIN rail DIN46277 (width: 35mm (1.38
"
)).
When removing the FX
2NC
-4AD, push downward on the DIN rail attachment
hook.
For further details, refer to the Handy Manual packed together with on the PLC
main unit.
3. PLC Connection
When connecting the FX
2NC
-
4AD to the FX
2NC
Series main
unit or extension block,
remove the extension port
cover from the right side of the
main unit or extension block,
keep the slide lock in the main
unit or extension block pulled
upward, then align the hook in
the FX
2NC
-4AD with the
mounting hole in the former
step of the main unit or
extension block.
Then push the slide lock downward to fix the FX
2NC
-4AD. When connecting two
or more FX
2NC
-4AD units, connect an FX
2NC
-4AD unit to another FX
2NC
-4AD
unit in the same way.
Up to four special function blocks or special function units in total can be
connected to the FX
2NC
Series PLC including those connected to the FX
2NC
-
CNV-IF.
For each connected special function block or special function unit, a unit number
is assigned starting with 0 for the special function block and special function unit
nearest to the main unit.
From the main unit, use FROM/TO instructions to read or write data stored in
the FX
2NC
-4AD.
Indication Description
PW Lit while 5 V power is normally supplied from PLC.
24 V
Lit while 24 V power is normally supplied to the "24+" and "24-"
power supply connector of the FX
2NC
-4AD.
A/D Flashes during A/D conversion.
PW
FX -4AD
2NC
24V
A/D
V1+
I1+
COM1
SLD
V2+
I2+
COM2
SLD
V3+
I3+
COM3
SLD
V4+
I4+
COM4
SLD
90(3.55")
20.2
(0.8")
V1+
I1+
COM1
SLD
V2+
I2+
COM2
SLD
V3+
I3+
COM3
SLD
V4+
I4+
COM4
SLD
74(2.92")
15
(0.6")
2)
1)
3)
6)
7)
5)
4)
3)’
Outer facing color: Munsell 0.08GY/7.54/0.81
Weight: Approx. 130g (0.29lbs)
(Includes terminal block)
Dimensions: mm(inch)
Terminal
arrangement
•
Main unit
Slide lock
Slide
lock
FX
2NC
-4AD
Hook
Hook
4. Wiring
4.1 Power supply wiring
Supply power (24V DC) to the FX
2NC
-4AD from the power supply connector.
When using the power supply connector, the following power cables are
available.
Power cables
FX
2NC
-10BPCB1:
Power crossover cable (offered as an accessory for the FX
2NC
-4AD)
FX
2NC
-100BPCB:
Power cable (offered as an accessory for the FX
2NC
Series main unit)
1) Connection example with the power supply through crossover wiring to the
FX
2NC
input extension block
2) Connection example to the external power supply
• Connect the " " terminal together with the ground terminal of the PLC main
unit to the ground of the power supply equipped with grounding resistance of
100
Ω
or less.
• For crossover wiring to the next block of the FX
2NC
-4AD, remove the resin
cover from the power crossover connector.
4.2 Input wiring
For terminal arrangement, refer to Chapter 2 of this manual.
FX
2NC
main unit
24+24-
Power supply
connector
DC24V ±10%
24+24-
FX
2NC
input extension block
Power
supply
connector
24+24-
24+24-
Power
circuit
AG
+15V-15V
FX
2NC
-4AD
Power
supply
connector
Power
supply
connector
Grounding
resistance
100Ω or less
Power crossover
cable FX
2NC
-
100BPCB
*1
Power crossover
cable FX
2NC
-
10BPCB1
Red*2Green
Connected to ground of the power supply
*1:Power terminal
*2:Black
Red*2
Red*2
24+24- 24+24-
Power
circuit
AG
+15V
-15V
FX
2NC
-4AD
DC24V ±10%
Power
supply
connector
Power
supply
terminal
FX
2NC
main unit
Power crossover
cable FX
2NC
-
100BPCB
Power supply
connector
Grounding
resistance
100Ω or less
Connected to the ground of
power supply
Red*1Green Red*1
*1:Black
V1+
COM1
I1+
SLD
V2+
COM2
*3
Shield *1
Current
input
Voltage
input
250Ω
6.8kΩ
CH1
FX
2NC
-4AD
I2+
200kΩ
*4
250Ω
6.8kΩ
CH2
200kΩ
*2
Input terminal block
SLD
*1 When wiring the analog output cable, use a shielded two-core twisted
cable, and separate it from other power cables and cables easily affected
by induction.
*2 The SLD terminal is connected to the
""
terminal inside the FX
2NC
-4AD.
*3 For current input, short-circuit the VO+ terminal and the IO+ terminal (O:
Input channel No.).
*4 Do not wire the
""
terminal.
Terminal connector handling
The FX
2NC
-4AD is equipped with a terminal connector whose form is
equivalent to that of the terminal connector type FX
2NC
PLC.
For the specifications of the suggested screwdriver, the dimensions of the
cable terminal, the external dimensions of the bar terminal equipped with
insulating sleeve, and applicable wiring, please refer to the FX
2NC
Handy
Manual.
5. Specifications
5.1 General specifications
The general specifications are equivalent to those of the PLC main unit.
(Please refer to the FX
2NC
Handy Manual.)
5.2 Power supply specifications
5.3 Performance specifications
5.4 Voltage/current input specifications
Item Specifications
Analog circuits 24V DC±10%, 130 mA, externally supplied.
Digital circuits
5V DC, 50 mA, supplied from the PLC main unit using an
extension port.
Item Specifications
Conversion speed 1 ms x Number of used channels
Isolated method
Photocoupler isolated analog input area from PLC.
Trans isolated power supply from analog I/O.
Channels are not isolated from each other.
Number of
occupied I/O
points
8 points (including input and output points)
Applicable PLC
FX
2NC
Series PLC
(Up to four units can be connected including special
function blocks and special function units connected to
FX
2NC
-CNV-IF.)
Built-in memory EEPROM
Item Voltage input Current input
Analog input
range
-10 to 10V DC
(input resistance: 200 kΩ)
Adjustment is enabled with
the following conditions:
Offset value: -10 to 9 V
Gain value: 10 V or less
"Gain - Offset": > 1 V
(except when
!
=2, 5, 8 is
set in BFM #0 that disables
all changes to the offset or
gain.)
Maximum absolute input:
±15 V
-20 to 20 mA DC, 4 to 20 mA DC
(input resistance: 250 Ω)
Adjustment is enabled with the
following conditions:
Offset value: -20 to 17 mA
Gain value: 30 mA or less
"Gain - Offset": > 3 mA
(except when
!
=2, 5, 8 is set in
BFM #0 that disables all changes
to the offset or gain.)
Maximum absolute input: ±30 mA
Digital output
Effective numeric value (15
bits) + Sign (1 bit)
Effective numeric value (14 bits) +
Sign (1 bit)
Resolution
0.32 mV (20 V × 1/64,000)
2.50mV (20 V × 1/8,000)
1.25
µ
A (40 mA × 1/32,000)
5.00
µ
A (40 mA × 1/8,000)
To t a l
accuracy
Ambient temperature:
25 °C ± 5 °C
±0.3% (±60 mV) against
full scale 20 V
Ambient temperature:
0 to +55 °C
±0.5% (±100 mV) against
full scale 20 V
Ambient temperature: 25°C ± 5°C
±0.5% (±200
µ
A) against full
scale 40 mA
4 to 20mA input is same (±200
µ
A)
Ambient temperature: 0 to +55°C
±1% (±400
µ
A) against full scale
40 mA
4 to 20mA input is same (±400
µ
A)
•
6. Buffer Memory (BFM)
Data transfer between the FX
2NC
-4AD and the PLC main unit is performed
via buffer memories (hereafter referred to as "BFM") of the FX
2NC
-4AD.
Each BFM consists of 1 word, 16 bits. BFM No. 0 to 1799 have assigned
functionality, communication with these BFMs should be performed using
TO/FROM instructions supplied by the PLC main unit.
When the power is switched ON from OFF, the initial value is written to each
BFM. Create a program for the PLC so that the desired contents are written
to the BFMs every time the power of the PLC is turned ON.
(The contents stored in BFM #0, #19, #22, #41 to #44 and #51 to #54 are
held in the built-in EEPROM, and kept against power failure.)
6.1 Buffer Memories (BFM) lists
BFM
No.
Description Initial value
#0 Specifies input mode of CH1 to CH4. H0000
#1 Reserved
#2
Number of averaging times for CH1
Setting range: 1 to 4,095 times
K1
#3
Number of averaging times for CH2
Setting range: 1 to 4,095 times
K1
#4
Number of averaging times for CH3
Setting range: 1 to 4,095 times
K1
#5
Number of averaging times for CH4
Setting range: 1 to 4,095 times
K1
#6 CH1: Digital filter setting Set range: 0 to 1,600 K0
#7 CH2: Digital filter setting Set range: 0 to 1,600 K0
#8 CH3: Digital filter setting Set range: 0 to 1,600 K0
#9 CH4: Digital filter setting Set range: 0 to 1,600 K0
#10 CH1 data (immediate data or average data)
#11 CH2 data (immediate data or average data)
#12 CH3 data (immediate data or average data)
#13 CH4 data (immediate data or average data)
•
•
•
Reserved
#19
Disables setting change of I/O characteristics
(BFM #0, BFM #1, BFM #21) and convenient
functions (BFM #22).
Disables change: K2, Enables change: K1
K1
#20
Initializes functions.
(Initializes functions at K1, then returns
automatically to K0 after initialization is
completed.)
K0
#21
Writes I/O characteristics. (Returns
automatically to K0 after write of offset/gain
value is finished.)
K0
#22
Sets convenient functions (data addition, upper/
lower limit value detection, sudden change
detection and minimum/maximum value hold).
K0
•
•
•
Reserved
#26
Upper/lower limit value error status (valid while
BFM #22 b1 is ON)
K0
#27
A/D data sudden change detection status (valid
while BFM #22 b2 is ON)
K0
#28 Scale over status K0
#29 Error status K0
#30 Model code (K2070) K2070
#31 Reserved
#32
Operating time 0 to 64,800 (s)
Subsequently, 64,800 is kept.
Measurement starts when the power is turned
on, and the measured value is reset when the
power is turned off.
K0
•
•
•
Reserved
#41 CH1 offset data (mV or µA) K0
#42 CH2 offset data (mV or µA) K0
#43 CH3 offset data (mV or µA) K0
#44 CH4 offset data (mV or µA) K0
•
•
•
Reserved
#51 CH1 gain data (mV or µA) K5000
#52 CH2 gain data (mV or µA) K5000
#53 CH3 gain data (mV or µA) K5000
#54 CH4 gain data (mV or µA) K5000
BFM
No.
Description Initial value
•
•
•
Reserved
#61
CH1 addition data Setting range: -16,000 to 16,000
(valid while BFM #22 b0 is ON)
K0
#62
CH2 addition data Setting range: -16,000 to 16,000
(valid while BFM #22 b0 is ON)
K0
#63
CH3 addition data Setting range: -16,000 to 16,000
(valid while BFM #22 b0 is ON)
K0
#64
CH4 addition data Setting range: -16,000 to 16,000
(valid while BFM #22 b0 is ON)
K0
•
•
•
Reserved
#71
CH1 lower limit error set value (valid while BFM #22
b1 is ON)
Minimum digital
value inside input
range
#72
CH2 lower limit error set value (valid while BFM #22
b1 is ON)
Minimum digital
value inside input
range
#73
CH3 lower limit error set value (valid while BFM #22
b1 is ON)
Minimum digital
value inside input
range
#74
CH4 lower limit error set value (valid while BFM #22
b1 is ON)
Minimum digital
value inside input
range
•
•
•
Reserved
#81
CH1 upper limit error set value (valid while BFM #22
b1 is ON)
Maximum digital
value inside input
range
#82
CH2 upper limit error set value (valid while BFM #22
b1 is ON)
Maximum digital
value inside input
range
#83
CH3 upper limit error set value (valid while BFM #22
b1 is ON)
Maximum digital
value inside input
range
#84
CH4 upper limit error set value (valid while BFM #22
b1 is ON)
Maximum digital
value inside input
range
•
•
•
Reserved
#91
CH1 sudden change detection set value
Setting range: 1 to 50% of full scale (valid while BFM
#22 b2 is ON)
5% of full scale
#92
CH2 sudden change detection set value
Setting range: 1 to 50% of full scale (valid while BFM
#22 b2 is ON)
5% of full scale
#93
CH3 sudden change detection set value
Setting range: 1 to 50% of full scale (valid while BFM
#22 b2 is ON)
5% of full scale
#94
CH4 sudden change detection set value
Setting range: 1 to 50% of full scale (valid while BFM
#22 b2 is ON)
5% of full scale
•
•
•
Reserved
#99
Clear of upper and lower limit value error and sudden
change detection error
K0
#100 Reserved
#101 CH1 minimum value (valid while BFM #22 b3 is ON)
#102 CH2 minimum value (valid while BFM #22 b3 is ON)
#103 CH3 minimum value (valid while BFM #22 b3 is ON)
#104 CH4 minimum value (valid while BFM #22 b3 is ON)
•
•
•
Reserved
#109 Minimum value reset K0
#110 Reserved
#111 CH1 maximum value (valid while BFM #22 b3 is ON)
#112 CH2 maximum value (valid while BFM #22 b3 is ON)
#113 CH3 maximum value (valid while BFM #22 b3 is ON)
#114 CH4 maximum value (valid while BFM #22 b3 is ON)
•
•
•
Reserved
#119 Maximum value reset K0
•
•
•
Reserved
6.2 Details of buffer memories
BFM #0: Specifies input mode.
Specify the input mode of CH1 to CH4 by writing a numeric
value to BFM #0.
The input mode specification declares, each BFM expressed
as a 4-digit hexadecimal code, and each channel No. is
assigned to each digit. Specify a numeric value 0 to F in
each digit for each channel.
!
=0:Voltage input mode (-10 to 10V
→
-32000 to 32000),
resolution 0.32mV
!
=1: Voltage input mode (-10 to 10V
→
-4000 to 4000), resolution 2.50mV
!
=2: Voltage input mode (-10 to 10V
→
-10000 to 10000),
resolution 1mV
!
=3: Current input mode (4 to 20mA
→
0 to 16000), resolution 1.25
µ
A
!
=4: Current input mode (4 to 20 mA
→
0 to 4000), resolution 5.00
µ
A
!
=5: Current input mode (4mA to 20mA
→
4000 to 20000), resolution 1.25
µ
A
!
=6: Current input mode (-20 to 20 mA
→
-16000 to 16000), resolution 1.25
µ
A
!
=7: Current input mode (-20 to 20 mA
→
-4000 to 4000), resolution 5.00
µ
A
!
=8: Current input mode (-20 to 20 mA
→
-20000 to 20000), resolution 1.25
µ
A
!
=9 to E:Unusable
!
=F:Corresponding CH is not used.
• The input characteristics are changed automatically according to the setting of
BFM #0. (The input characteristics can be changed to independent values
except when
!
=2, 5, 8 is set in BFM #0 that disables all changes to the offset or
gain.
)
• It takes approximately 5 seconds to change the input mode (to change each
set value).
Time interval of 5 seconds or more after changing the input mode until the
write of each setting (TO instruction) is performed.
•
Setting "HFFFF" to allocate all channels as unusable is not allowed.
BFM #2 to BFM #5: Number of averaging times
(Make sure to set the number of averaging times to "1" when using the digital
filer.)
The allowable set range of the number of averaging times is 1 to 4,095.
If the number of averaging times is set to "1", the immediate data (current value)
is stored in BFM #10 to #13. Otherwise, BFM #10 to BFM #13 will be averaged
depending on the value set in BFM #2 to BFM #5.
If the number of averaging times is set to "0" or less, "0" is written. If the number
of averaging times is set to "4,096" or more, "4096" is written. In either case,
number of averaging times setting error (BFM #29 b10) occurs. The initial set
value is "1".
Average data update
• When the number of averaging times (BFM #2 to BFM #5) is set to "400" or
less, the average (BFM #10 to BFM #13) is updated every time the A/D
conversion processing is performed.
The update time is as follows:
Average data update time = (A/D conversion time) x Number of channels
• When the number of averaging times (BFM #2 to BFM #5) is set to "401" or
more, the average (BFM #10 to BFM #13) is updated every time the A/D
conversion is performed by as many as the set number of averaging times.
The update time is as follows:
Average data update time = (A/D conversion time) x Number of channels x
Number of averaging times
In either case above, until the number of A/D conversion times reaches the set
number of averaging times for the first time, the average at each time point is
stored in BFM #10 to BFM #13.
BFM #6 to BFM #9: Digital filter setting
(Effective only when the number of averaging times is set to "1")
Setting BFM #6 to BFM #9 to "1" invokes, the digital filter which can be provided
for each channel. If the fluctuation of the analog input value is less than the set
value of BFM #6 to #9, the analog input value is converted into a stabilized
digital output value. If the analog input value exceeds the set value, the
proceeding digital conversion value will follow and replicate there values. The
data is updated every "5ms x Number of channels", and stabilized by the last 20
data.
#198
Data history sampling time
[Effective only for channels whose number of
averaging times (BFM #2 to #5) is 1 and digital filter
setting (BFM #6 to #9) is 0]
Setting range: 0 to 30,000 ms
K0
#199
Resets or stops data history.
[Effective only for channels whose number of
averaging times (BFM #2 to #5) is 1 and digital filter
setting (BFM #6 to #9) is 0]
K0
#200 CH1 data history (1st value) Data history sampling
is effective only for
channels whose
number of averaging
times (BFM #2 to #5)
is 1 and digital filter
setting (BFM #6 to #9)
is 0.
K0
•
•
•
•
•
•
•
•
•
#1799
CH4 data history (400th
value)
K0
BFM
No.
Description Initial value
BFM#0
H
!!!!
CH1
CH2
CH3
CH4
By this function, unstable analog values can be converted into stable digital
values.
The table below shows the relationship between the set value of BFM #6 to
#9 and the operation.
BFM #10 to BFM #13: Channel data
The A/D conversion data for each channel is written to BFM #10 to #13.
BFM #19: Disables setting change
BFM #19 enables or disables the setting change of the I/O characteristics
(BFM #0, #41 to #44, #51 to #54), the convenient functions (BFM #22).
K1: Enables change (factory default).
K2: Disables change.
BFM #20: Initializes functions
BFM #20 initializes all data stored in BFM #0 to BFM #1799, and sets the
FX
2NC
-4AD to factory default.
By initialization, the input characteristics are reset to the values set at
factory default (voltage input, offset value K0, gain value K5000).
K0: Normal
K1: Executes initialization. (Writes K1, subsequently returns to K0
when initialization is completed.)
BFM #21: Writes I/O characteristics
Each channel No. is assigned to the lower 4 bits of BFM #21.
When a bit is set to ON, the offset data (BFM #41 to BFM #44) and the gain
data (BFM #51 to BFM #54) of the assigned channel No. are written to the
built-in memory (EEPROM).
Give the write command to two or more channels at a time. (When entering
"HF", all channels are written to.)
When the write is completed, BFM #21 subsequently returns to K0.
BFM #22: Sets convenient functions
The functions described below are assigned to b0 to b3 of BFM #22. When
a bit is set to ON, the assigned function becomes valid.
When a bit is set to OFF, the assigned function becomes invalid.
b0: Data addition function
The data (BFM #10 to BFM #13), minimum/maximum value (BFM #101
to BFM #104, BFM #111 to BFM #114) and data history (BFM #200 to
BFM #1799) of each channel is the measured value added by the
addition data (BFM #61 to BFM #64).
When using this function, enter the value added by the addition data
(BFM #61 to BFM #64) to the lower limit value error set value (BFM
#71 to BFM #74) and the upper limit value error set value (BFM #81 to
BFM #84).
The addition data (BFM #61 to BFM #64) is not added to the scale over
data (BFM #28).
b1: Upper/lower limit value detection function
When the A/D conversion data of each channel is outside the range of
the lower limit value error set value (BFM #71 to BFM #74) to the upper
limit value error set value (BFM #81 to BFM #84), the result is written to
the upper/lower limit value error status (BFM #26).
b2: Sudden change detection function
When the data (BFM #10 to BFM #13) of each channel is updated, if
the difference between the previous value and the new value is larger
than the sudden change detection set value (BFM #91 to BFM #94),
the result is written to the sudden change detection status (BFM #27).
b3: Minimum/maximum value hold function
The minimum value of the data (BFM #10 to BFM #13) of each channel
is written to BFM #101 to BFM #104, and the maximum value is written
to BFM #111 to BFM #114.
BFM #26: Upper/lower limit error status
The upper /lower limit value detection function (BFM#22 b1), writes
detected errors to the corresponding bits in BFM#26 (see table). Upper and
lower limit error status for the four channels is located in bit-pairs in the first
8bits of BFM#26.
When the data (BFM #10 to BFM #13) of any channel is outside the range
from the lower limit error value (BFM #71 to BFM #74) to the upper limit
error value (BFM #81 to BFM #84), the corresponding bit turns ON.
When a bit turns ON, it remains ON until it is reset by BFM #99 or the
power is turned OFF.
Set value < 0
Digital filter function is invalid. Set value error occurs
(BFM #29 b11 turns ON.).
Set value = 0 Digital filter function is invalid.
1 ≤ Set value ≤ 1,600 Digital filter function is valid.
1,600 < Set value
Digital filter function is invalid. Set value error occurs
(BFM #29 b11 turns ON.).
Analog
value
Digital filter set value
Analog input value
They are converted into stable digital output values.
The digital output value follows up the
analog input value.
Time
Digital output value
BFM21
b15, b14, b13, b12, b11, b10, b9, b8, b7, b6, b5, b4, b3, b2, b1, b0
CH4
CH3
CH2 CH1
Invalid
Thank you very much for purchasing this product.
FX
2NC
-4AD Analog input block
In order to handle the product properly please read this manual thoroughly
before starting to use the product.
User’s Manual
MODEL FX
2NC
-4AD
MANUAL Number JY997D07801A
Date June 2003