Mitsubishi Electronics FXavc-4DA TV Converter Box User Manual


 
Guidelines for the Safety of the User and Protection of the FX
2NC
-4DA
special function block.
This manual should be used by trained and competent personnel. The
definition of such a person or persons is as follows:
a)Any engineer using the product associated with this manual, should be
of a competent nature, trained and qualified to the local and national
standards. These engineers should be fully aware of all aspects of
safety with regards to automated equipment.
b)Any commissioning or service engineer must be of a competent nature,
trained and qualified to the local and national standards.
c)All operators of the completed equipment should be trained to use this
product in a safe and coordinated manner in compliance to established
safety practices.
Note:
The term `completed equipment' refers to a third party constructed
device which contains or uses the product associated with this
manual.
Note concerning the CE marking
CE Marking does not guarantee that an entire mechanical module
produced in accordance with the contents of the notification comply with
the following standards. Compliance to EMC standards of the entire
mechanical module should be checked by the user / manufacturer.
Standards with which this product complies
Type : Programmable Controller (Open Type Equipment)
Models : Products manufactured starting April 1st, 2003.
For more details please contact the local Mitsubishi Electric sales site.
- Notes for compliance to EMC regulation.
It is necessary to install the FX
2NC
-4DA in a shielded metal control panel.
For further information manual concerning the FX Series, refer to the
following table.
List of Further Information Manuals
Electromagnetic Compatibility
Standards (EMC)
Remark
EN61000-6-4:2001
Electromagnetic compatibility
-Generic standards - Emission
standard for Industrial environment
Compliance with all relevant aspects
of the standard. (Radiated Emissions
and Mains Terminal Voltage
Emissions)
EN61000-6-2:2001
Electromagnetic compatibility
-Generic standards Immunity for
industrial environments.
Compliance with all relevant aspects
of the standard. (RF immunity, Fast
transients, ESD, Conducted, Surges,
Power magnetic fields, Voltage dips
and Voltage interruptions)
Manual Name Manual No. Description
FX
2NC
Hardware
Manual
JY992D76401
This manual contains hardware explanations
of wiring, installation and specifications for
the FX
2NC
Series programmable controllers.
FX
Programming
Manual
II
JY992D88101
This manual contains instruction
explanations for the FX
1S
, FX
1N
, FX
2N
and
FX
2NC
Series programmable controllers.
1. Introduction
The FX
2NC
-4DA analog output block (hereafter referred to as "FX
2NC
-4DA")
converts 4 digital values (from the PLC main unit) into analog output values
(voltage or current).
The FX
2NC
-4DA can be connected to the FX
2NC
Series PLC.
1) Each analog output channel can be configured for voltage output, or current
output. The output mode must be set using the TO instruction and the
appropriate connection method.
A different analog output can be selected for each channel.
2) The voltage output ranges from -10 to 10 V. The current output ranges from
4 to 20 mA and from 0 to 20 mA. The output characteristics can be adjusted
for each channel.
3) The resolution is 5 mV (10 V × 1/2000) when the voltage output is used, 20
µA (20 mA × 1/1000) when the current output is used.
4) Data transfer with the PLC is performed via the buffer memories of the
FX
2NC
-4DA by FROM/TO instructions.
2. External Dimensions and Part Name
Accessory:Special function block number label, Power crossover cable
FX
2NC
-10BPCB1
1)Status indicator LED 2)Terminal connector (European type)
3),3)’Extension port 4)Slide lock for extension block
5)DIN rail clip 6)Power supply connector (24V DC)
7)Power supply connector (Supply for extension block)
The connector 3)' is equipped with a cover.
- Never wire the terminals.
• Status indicator LED
• Install the FX
2NC
-4DA on the right side of the main unit, extension block or
special function block of the FX
2NC
Series PLC.
• DIN rail installation
The FX
2NC
-4DA can be installed on DIN rail DIN46277 (width: 35mm (1.38
"
)).
When removing the FX
2NC
-4DA, push downward on the DIN rail attachment
hook.
For further details, refer to the Handy Manual packed together with the PLC
main unit.
Indication Description
PW Lit while 5 V power is normally supplied from PLC.
24 V
Lit while 24 V power is normally supplied to "24+" and "24-"
terminals of the FX
2NC
-4DA.
D/A Flashes during D/A conversion.
PW
FX -4DA
2NC
24V
D/A
V1+
I1+
COM1
V2+
I2+
COM2
V3+
I3+
COM3
V4+
I4+
COM4
24-
24-
24+
24+
24.2
(0.96")
90(3.55")
74(2.92")
15
(0.60")
2)
1)
3)
6)
7)
5)
4)
3)’
V1+
I1+
COM1
V2+
I2+
COM2
V3+
I3+
COM3
V4+
I4+
COM4
24-
24-
24+
24+
Outer facing color: Munsell 0.08GY/7.54/0.81
Weight: Approx. 130g (0.29lbs)
(Includes terminal block)
Dimensions: mm(inch)
Terminal
arrangement
3. PLC Connection
When connecting the FX
2NC
-
4DA to the FX
2NC
Series main
unit or extension block,
remove the extension port
cover from the right side of the
main unit or extension block,
keep the slide lock in the main
unit or extension block pulled
upward, then align the hook in
the FX
2NC
-4DA with the
mounting hole in the former step of the main unit or extension block.
Then, push the slide lock downward to fix the FX
2NC
-4DA. When connecting two
or more FX
2NC
-4DA units, connect an FX
2NC
-4DA unit to another FX
2NC
-4DA
unit in the same way.
Up to four special function blocks or special function units in total can be
connected to the FX
2NC
Series PLC including those connected to the FX
2NC
-
CNV-IF. For each connected special function block or special function unit, the
unit number is assigned starting with 0 for the special function block and special
function unit nearest to the main unit. From the main unit, use the FROM/TO
instructions to read or write data stored in the FX
2NC
-4DA.
4. Wiring
4.1 Power supply wiring
Supply power (24V DC) to the FX
2NC
-4DA to either the power supply connector
or the power supply terminal.
When using the power supply connector, the following power cables are
available.
Power cables
FX
2NC
-10BPCB1:
Power crossover cable (offered as an accessory for the FX
2NC
-4DA)
FX
2NC
-100BPCB:
Power cable (offered as an accessory for the FX
2NC
Series main unit)
1) Connection example with the power supply through the crossover connector
of the FX
2NC
input extension block
2) Connection example to the external power supply through the power supply
connector
Main unit
Slide lock
Slide
lock
FX2NC-4DA
Hook
Hook
FX
2NC
main unit
24+24-
Power supply
connector
DC24V±10%
Grounding
resistance
100
or less
24+24-
FX
2NC
input extension block
Power crossover
cable FX
2NC
-
100BPCB
Power
supply
connector
*1
Power crossover
cable FX
2NC
-
10BPCB1
Power
supply
connector
Red*2Green
24+24-
24+24-
Power
circuit
AG
+15V
-15V
FX
2NC
-4DA
24+
24-
Connected to ground of the power
supply
Power
supply
connector
*1:Power supply terminal
*2:Black
Red*2
Red*2
Power
supply
connector
Power
supply
terminal
FX
2NC
main unit
Power crossover
cable FX
2NC
-
100BPCB
24+24-
Power supply
connector
DC24V±10%
Grounding
resistance
100
or less
Connected to the ground of
power supply
24+24-
Power
circuit
AG
+15V-15V
FX
2NC
-4DA
24+
24-
Red*1Green Red*1
*1:Black
3) Connection example to the external power supply through the power
supply terminal
• Do not use both the power supply connector and the power supply
terminal at the same time.
• Connect the " " terminal, and the ground terminal of the PLC main unit
to the ground of the power supply equipped with grounding resistance of
100 or less.
• "24+" and "24-" of the power supply connector and the power supply
terminal are connected inside the FX
2NC
-4DA respectively.
• For crossover wiring to the next block of the FX
2NC
-4DA, remove the resin
cover from the power supply connector.
4.2 Output wiring
For terminal arrangement, refer to Chapter 2 of this manual.
*1 When wiring the analog output cable, use a shielded two-core twisted
cable, and separate it from other power cables and cables easily affected
by induction.
*2 Ground the shielded cable at one point on the signal receiving side.
(Grounding resistance 100
or less)
*3 If the output contains noise and ripple, connect a capacitor of
approximately 0.1 to 0.47
µ
F, 25 V.
*4 Do not short-circuit the voltage output terminal. Do not connect a load for
the current output to the voltage output terminal.
*5 Do not wire the
""
terminal.
• Mixed outputs (voltage output and current output) in the same channel
are not allowed.
Terminal connector handling
The FX
2NC
-4DA is equipped with a terminal connector whose from is
equivalent to that of the terminal connector type FX
2NC
PLC.
For the specifications of the suggested screwdriver, the dimensions of the
cable terminal, the external dimensions of the bar terminal equipped with
insulating sleeve, and applicable wiring, refer to the FX
2NC
Handy Manual.
Power
circuit
FX
2NC
main unit
24+24-
Power supply
connector
DC24V±10%
Power
supply
terminal
24+24-
AG
+15V-15V
FX
2NC
-4DA
24+
24-
Power
supply
connector
Connected to the ground
of power supply
Red*1Green
*1:Black
Grounding
resistance
100
or less
V1+
COM1
I1+
V2+
COM2
Shield *1
Current output
Voltage output
CH1
FX
2NC
-4DA
I2+
*5
CH2
Output terminal block
Inverter, etc.*3
Recorder, etc.
*2
*4
5. Specifications
5.1 General specifications
The general specifications are equivalent to those of the PLC main unit.
(Refer to the FX
2NC
Handy Manual.)
5.2 Power supply specifications
5.3 Performance specifications
Item Specifications
Analog circuits 24 V DC±10%, 130 mA, externally supplied
Digital circuits
5 V DC, 30 mA, supplied from the PLC main unit using an
extension port
Item Voltage output Current output
Analog
output range
-10V DC to 10V DC (External
load resistance: 2k
to 1M
).
DC 0mA to 20mA (External
load resistance: 500
or less).
Digital input
Effective numeric value
(11 bits) + Sign (1 bit)
Effective numeric value
(10 bits) + Sign (1 bit)
Resolution 5mV (10V
×
1/2000) 20
µ
A (20mA
×
1/1000)
To t a l
accuracy
25
°
C ± 5
°
C; ±0.5%
(at full scale of 20V)
0
°
C to 55
°
C; ±1.0%
(at full scale of 20V)
(Excluding load fluctuation)
25
°
C ± 5
°
C; ±0.5%
(at full scale of 16mA)
0
°
C to 55
°
C; ±1.0%
(at full scale of 16mA)
Conversion
speed
2.1ms for 4 channels (A change in the number of channels
used will not change the conversion speed.)
Isolated
method
Analog output and PLC are isolated by photocoupler. Power
supply and analog output are isolated by transformer.
(Channels are not isolated from each other.)
Number of
occupied I/O
points
8 points. (Including input and output points)
Applicable
PLC
FX
2NC
Series PLC
(Up to four units can be connected including special function
blocks and special function units connected to FX
2NC
-CNV-IF.)
Built-in
memory
EEPROM
I/O
characteristics
(Default:
mode 0)
(I/O
characteristics
can be
adjusted
using the
procedure
described in
Section 9 in
this manual.)
Mode 0 (Voltage output: -10V to 10V)
At the load resistance of 10k
Mode 1 (Current output: 4mA to 20mA)
At the load resistance of 250
Mode 2 (Current output: 0mA to 20mA)
At the load resistance of 250
A command sent from the programmable controller can
change the mode. The voltage/current output mode selected
will determine the output terminals used.
A n a lo g o u tp u t
D ig ita l in p u t
1 0 V
1 0 . 2 3 5 V
- 2 ,0 0 0
2 ,0 0 0
- 1 0 V
- 1 0 .2 4 V
- 2 ,0 4 8
2 ,0 4 7
A n a lo g
o u t p u t
4 m A
D ig ita l in p u t
2 0 m A
0
1 ,0 0 0
A n a lo g
o u t p u t
D ig ita l in p u t
2 0 m A
0
1 ,0 0 0
6. Buffer Memory (BFM)
The FX
2NC
-4DA exchanges data with the PLC via the buffer memory addresses
(16-bit data) in the FX
2NC
-4DA.
BFM #0 to #5, #8 to #17, #20 and #21 can be written by the PLC using the TO
instruction. BFM #29 and #30 can be read using the FROM instruction.
6.1 Buffer Memories (BFM) lists
*1 The status of BFM #0, #5, and #21, will be written to EEPROM, therefore the
set values will be retained even after turning OFF the power.
*2 Offset data:Actual analog output value when corresponding output data (BFM
#1 to #4) is 0
*3 Gain data: Actual analog output value when corresponding output data (BFM
#1 to #4) is 1,000
*4 When current output mode 1 (4 mA to 20 mA) is set, the offset data will be
automatically set to 4,000 and the gain data to 20,000. When the current output
mode 2 (0 mA to 20 mA) is set, the offset data will be automatically set to 0 and
the gain data to 20,000.
[BFM #0] Output mode select
The value of BFM #0 switches the analog output between voltage and current
for each channel. It takes the form of a 4 digit hexadecimal number. The first
digit will be the command for channel 1 (CH1), and the second digit for channel
2 (CH2) etc. The numeric values of these four digits respectively represent the
following items:
O = 0:Sets the voltage output mode (-10 V to 10 V).
O = 1:Sets the current output mode (4 mA to 20 mA).
O = 2:Sets the current output mode (0 mA to 20 mA).
Switching the output mode resets the I/O characteristics to the factory-default
characteristics. Refer to the performance specifications described in section 5.
Example: H2110CH1: Voltage output (-10 V to 10 V)
CH2 and CH3: Current output (4 mA to 20 mA)
CH4: Current output (0 mA to 20 mA)
[BFM #1, #2, #3 and #4] Output data channels CH1, CH2, CH3, and CH4
BFM #1: Output data of CH1 (Initial value: 0)
BFM #2: Output data of CH2 (Initial value: 0)
BFM #3: Output data of CH3 (Initial value: 0)
BFM #4: Output data of CH4 (Initial value: 0)
[BFM #5] Data holding mode
While the programmable controller is in the STOP mode, the last output value in
the RUN mode will be held. To reset the value to the offset value, write the
hexadecimal value in BFM #5 as follows:
O = 0: Holds the output.
O = 1: Resets to the offset value.
Example: H0011 CH1 and CH2 = Offset value CH3 and CH4 = Output holding
BFM No. Description
#0 *1 Output mode select. Factory setting H0000
#1 Output data CH1
#2 Output data CH2
#3 Output data CH3
#4 Output data CH4
#5 *1 Data holding mode. Factory setting H0000
#6, #7 Reserved
#8 Offset/gain setting command CH1, CH2 Initial value H0000
#9 Offset/gain setting command CH3, CH4 Initial value H0000
#10 Offset data CH1 *2
Unit: mV or
µ
A
Initial offset value: 0
Initial gain value: 5,000 *4
#11 Gain data CH1 *3
#12 Offset data CH2 *2
#13 Gain data CH2 *3
#14 Offset data CH3 *2
#15 Gain data CH3 *3
#16 Offset data CH4 *2
#17 Gain data CH4 *3
#18,#19 Reserved
#20 Initialize. initial value = 0
#21 *1 I/O characteristics adjustment inhibit (Initial value b1=0, b0=1)
#22 to #28 Reserved
#29 Error status
#30 K3020 identification code
#31 Reserved
C H 4 C H 3 C H 2 C H 1
H
C H 4 C H 3 C H 2 C H 1
H
[BFM #8 and #9] Offset/gain setting command
Changes offset and gain values of channels CH1 to CH4 by writing 1 to the
corresponding Hex digits of BFM #8 or #9. The current values will be valid until
this command is output. (Refer to Chapter 9)
1 to 4: Channel number O = 0: No changes done. O = 1: Change data value.
[BFM #10 to #17] Offset/gain data
The offset and gain values are changed by writing new data to BFM #10 to #17.
The units of the data to be written are mV or µA. The data should be written and
then BFM #8 and #9 set. Note that the data value will be rounded down to the
nearest 5mV or 20µA.
[BFM #20] Initialize
When K1 is written in BFM #20, all values will be returned to the factory-default.
(Note that the BFM #20 data will override the BFM #21 data.)
This initialize function is convenient if you have an error in adjustment.
[BFM #21] I/O characteristics adjustment inhibit
Setting BFM #21 to K2 inhibits the user from inadvertent adjustment of I/O
characteristics. The adjustment inhibit function, once set, will be valid until the
Permit command (BFM #21=K1) is set. The initial value is K1 (Permit). The set
value will be retained even after power-OFF.
[BFM #29] Error status
When an error occurs, use the FROM command to read out the details of the
error.
Error status
Bits b4 to b9, b11, b13 to b15 are not defined.
[BFM #30] Identification code
The identification code for a special function block is read using the FROM
instruction. The identification code for the FX
2NC
-4DA unit is K3020.The main
unit can use this facility in the program to identify the special function block
before commencing any data transfers from and to the special function block.
Note:
Values of BFM #0, #5, and #21, are stored in the EEPROM memory of the
FX
2NC
-4DA. BFM #10 to #17 are copied to EEPROM when the gain/offset
setting command BFM #8, #9 is used. Also, BFM #20 causes the resetting of
the EEPROM memory. The EEPROM has a life of about 10,000 cycles
(changes), so do not use programs which frequently change these BFMs.
A mode change of BFM #0 automatically involves a change of the
corresponding offset and gain values. Because of the time needed to write the
new values to the internal EEPROM memory, a delay of 3 s is required between
instructions changing BFM #0 and instructions writing to the corresponding
BFM #10 through BFM #17.
Therefore, a delay timer should be used before writing to BFM #10 through #17.
(Refer to chapter 9.)
Bit Name
Status when bit is set to "1"
(turned ON)
Status when bit is set
to "0" (turned OFF)
b0 Error
Error if any of b1 to b4 is turned
ON
No error
b1 O/G error
Offset/gain data in EEPROM is
abnormal or a data setting error
occurs.
Offset/Gain data normal
b2
Power supply
error
24V DC power failure
Power supplied
normally
b3
Hardware
error
Defective D/A converter or other
hardware
Functioning hardware
b4 Program error
FROM/TO instruction is used by
mistake.
Program is normal.
b10 Range error
The digital input or analog output
value is out of the specified range.
The input or output
value is in the specified
range.
b12
G/O-
Adjustment
prohibit status
BFM #21 is not set to "K1". Adjustable status
G 2
H
O 2 G 1
O 1
G 4
H
O 4 G 3
O 3
BFM #8
BFM #9
7. Operation and Program Examples
If the factory-default I/O characteristics are not changed and the status
information is not used, you can operate the FX
2NC
-4DA using the following
simple program. For the FROM and TO instructions, refer to the FX
Programming Manual (II).
CH1 and CH2: Voltage output mode (-10 V to 10 V)
CH3 : Current output mode (4 mA to 20 mA)
CH4 : Current output mode (0 mA to 20 mA)
7.1 Operation procedure
1) Turn OFF the power of the PLC, and then connect the FX
2NC
-4DA. After
wards, wire the I/O lines of the FX
2NC
-4DA.
2) Set the PLC to STOP, and turn ON the power. Write the above program
then switch the PLC to RUN.
3) Analog values will be sent from D0 (BFM #1), D1 (BFM #2), D2 (BFM
#3), and D3 (BFM #4) to the respective output channels of the FX
2NC
-
4DA. When the PLC is in STOP, the analog values set before stopping
the PLC will remain output. (The output will be held.)
4) When the PLC is in STOP, the offset values can also be output. For a
detailed description, refer to Section 6).
7.2 Program example
In the example shown below, CH1 and CH2 in the FX
2NC
-4DA, connected
to the special function block No. 0, are handled as the voltage output, CH3
is handled as the current output (4 to 20 mA), CH4 is handled as the
current output (0 to 20 mA), and these outputs are held when the PLC is
stopped. In the example shown below, the status information is utilized.
8. Caution Regarding Operation
1) Check whether the output wiring and/or the FX
2NC
-4DA is properly
connected to the FX
2NC
main unit.
2) The FX
2NC
-4DA uses 30mA (5V) supplied from the main unit.
Confirm that the total value including the 5V current consumption of
other special function blocks is less than the limit.
3) The FX
2NC
-4DA starts operation when the 24V DC power is set to ON.
Make such a program that changes over the output of the BFM #0
before writing the output data.
4) After the 24V DC power for the FX
2NC
-4DA is turned ON or OFF, the
analog output may fluctuate for approximately 1 second. This is due to
time delays in the power supply from the main unit or differences in start
time. For this reason, be sure to take preventive measures so that this
output fluctuation will not affect the external units.
[Example of preventive measure]
M8002
initial pulse
TO K0 K0 H2100 K1
Write the data for CH1 to
D0, CH2 to D1, CH3 to D2
and CH4 to D3.
TO K0 K1 D0 K4
M8000
RUN
monitor
Write data in respective data registers while
observing the following ranges:
Data register D0 and D1: -2,000 to 2,000
Data registers D2 and D3: 0 to 1,000
(H2100)
BFM #0
CH1 and CH2: Voltage output
CH3: Current output (4mA to 20 mA)
CH4: Current output (0 mA to 20 mA)
Data register D0
BFM #1 (output to CH1)
Data register D1
BFM #2 (output to CH2)
Data register D2
BFM #3 (output to CH3)
Data register D3
BFM #4 (output to CH4)
K1
K1
K4
K1
No error
M1
M10
M8000
Normal output range
FROM
FROM
K0
K3020
K0
K0
K0
K30
D4
K0
K1
K29
D4
M0
H2100
D0
K4M10
Writes -2,000 to 2,000 to D0 and D1.
Writes 0 to 1,000 to D2 and D3.
P
M3
RUN
monitor
CMP
TO
M20
T
O
BFM #30 (model code) of the
block No. 0 Transferred to D4.
When the code No. is K3020
(FX
2NC-4DA), M1 turns ON.
H2100
BFM #0 (unit No. 0)
CH1 and CH2: Voltage output
CH3: Current output (4 to 20 mA)
CH4: Current output (0 to 20 mA)
D0
BFM #1 (CH1 output)
D1
BFM #2 (CH2 output)
D2
BFM #3 (CH3 output)
D3
BFM #4 (CH4 output)
BFM #29 (b15 to b0)
M10 to M25
The status information is read.
The output data is normal.
2 4 V D C p o w e r
s u p p ly
F X - 4 D A s p e c ia l
fu n c tio n b lo c k
2 N C
A n a lo g d a ta
c u t O F F c ir c u it
E x te rn a l
a n a lo g u n it
P o w e r s w itc h
Thank you very much for purchasing this product.
FX
2NC
-4DA Analog output block
In order to handle the product properly please read this manual thoroughly
before starting to use the product.
User’s Manual
MODEL FX
2NC
-4DA
MANUAL Number JY997D07601A
Date June 2003