Mitsubishi Electronics LY42NT1P Universal Remote User Manual


 
29
CHAPTER 4 SPECIFICATIONS
4
4.2 Input Module Specifications
4.2 Input Module Specifications
4.2.1 LX10 AC input module
Item Specifications Appearance
Number of input points 16 points
Rated input voltage, frequency 100 to 120VAC (+10%/-15%), 50/60Hz(±3Hz)
Input voltage distortion Within 5%
Rated input current 8.2mA (100VAC, 60Hz), 6.8mA (100VAC, 50Hz)
Inrush current Max. 200mA within 1ms
ON voltage/ON current 80VAC or higher/5mA or higher (50Hz, 60Hz)
OFF voltage/OFF current 30VAC or lower/1.7mA or lower (50Hz, 60Hz)
Input resistance 12.2k (60Hz), 14.6k (50Hz)
Response time
OFF to ON 15ms or less (100VAC 50Hz, 60Hz)
ON to OFF 20ms or less (100VAC 50Hz, 60Hz)
Dielectric withstand voltage 1400VAC, 1 minute (altitude 2000m)
Insulation resistance 10M or more by insulation resistance tester
Noise immunity
By noise simulator of 1500Vp-p noise voltage, 1µs noise width and 25 to 60Hz
noise frequency
Protection degree IP1X
Common terminal arrangement 16 points/common (common terminal: TB17)
Number of occupied I/O points 16 points (I/O assignment: input 16 points)
External interface
18-point screw terminal block (M3 × 6 screws) ( Page 62, Section 6.2.1)
5VDC internal current consumption 90mA (TYP. all points ON)
Weight 0.17kg
Derating chart
6002040
0
Input voltage
16 points, 50
16 points, 55
15 points, 55
Ambient temperature( )
Simultaneous
on input
points
(points)
4
16
12
8
to 132VAC to 120VAC
- to 132VAC