Appendix 2.1 OFFGAN
Switches the mode of the A/D converter module. (Normal mode to offset/gain setting
mode, offset/gain setting mode to normal mode)
Usable devices
Internal device
(System, user)
MELSECNET/H
Direct J \
Constant
Set data
Bit Word
File
register
Bit Word
Special
function
module
U
\G
Index
register
Z
K, H S
Other
(S) ———
G.OFFGAN
Command
G.OFFGAN
Command
GP.OFFGAN
(S)
(S)
[Instruction
symbol]
[Execution
condition]
Un
UnGP.OFFGAN
Set data
Device Description Setting range Data type
Un Start I/O number of the module 0 to FE
H
Binary 16 bits
(S)
Mode switching
0: Switching to normal mode
1: Switching to offset/gain setting mode
The setting of any other value results in "switching to
offset/gain setting mode".
0 ,1 Binary 16 bits
(1) Function
Switches the mode of the A/D converter module.
• Normal mode to offset/gain setting mode (the offset/gain setting mode status
flag (XA) turns ON)
• Offset/gain setting mode to normal mode (the offset/gain setting mode status
flag (XA) turns OFF)
POINT
(1) When the offset/gain setting mode is switched to the normal mode, Module
Ready (X0) turns from OFF to ON.
Note that initial setting processing will be executed if there is a sequence
program that makes initial setting when Module Ready (X0) turns ON.
(2) When the offset/gain setting mode is switched to the normal mode, the A/D
converter module holds the previous operation condition and resumes
operation automatically under the previous operation condition.
(2) Operation error