Q68DAV, Q68DAI
D/A Converter Module
Thank you for buying the Mitsubishi general-purpose programmable logic
controller MELSEC Q Series.
Prior to use, please read both this manual and detailed manual thoroughly
and familiarize yourself with the product.
User's Manual
(Hardware)
MODEL Q- 68D/A -U-H-JE
MODEL
Number
13JT24
IB-0800151-B (0509) MEE
©2000 MITSUBISHI ELECTRIC CORPORATION
SAFETY PRECAUTIONS
(Read these precautions before using.)
When using Mitsubishi equipment, thoroughly read this manual and the associated
manuals introduced in the manual. Also pay careful attention to safety and handle the
module properly.
These precautions apply only to Mitsubishi equipment. Refer to the user’s manual of the
CPU module to use for a description of the PLC system safety precautions.
These SAFETY PRECAUTIONS classify the safety precautions into two
categories: "DANGER" and "CAUTION".
DANGER
Procedures which may lead to a dangerous condition and
cause death or serious injury if not carried out properly.
CAUTION
Procedures which may lead to a dangerous condition and
cause superficial to medium injury, or physical damage only,
if not carried out properly.
Depending on circumstances, procedures indicated by CAUTION may also be linked
to serious results.
In any case, it is important to follow the directions for usage.
Store this manual in a safe place so that you can take it out and read it whenever
necessary. Always forward it to the end user.
Conformance to the EMC Directive/Low Voltage Directive
When incorporating the Mitsubishi PLC into other machinery or equipment and keeping
compliance with the EMC and low voltage directives, refer to Chapter 3, "EMC
Directives and Low Voltage Directives" of the User's Manual (Hardware) included with
the CPU module or base unit used.
The CE logo is printed on the rating plate on the main body of the PLC that conforms to
the EMC directive and low voltage instruction.
By making this product conform to the EMC directive and low voltage instruction, it is not
necessary to make those steps individually.
1. Overview
This manual explains specifications and the names of the components for the
Q68DAV type D/A converter module (hereafter Q68DAV) and the Q68DAI
type D/A converter module (hereafter Q68DAI) which are used in combination
with the MELSEC-Q Series CPU module. In this manual, both the Q68DAV
and Q68DAI are referred to as D/A converter modules.
After unpacking, confirm that the following products are enclosed.
Part name Qty.
Q68DAV/Q68DAI Model Digital-Analog module 1
FG terminal L-shaped metal fitting 1
2. Specifications
The specifications for the D/A converter module are shown in the following
table. For general specifications, refer to the operation manual for the CPU
module being used.
T
yp
e
Item
Q68DAV Q68DAI
Number of analog outputs 8 points (8 channels)
Digital input 16-bit signed binary (normal resolution
mode: –4096 to 4095,
high resolution mode:–12288 to
12287, –16384 to 16383)
16-bit signed binary (normal
resolution mode: –4096 to 4095,
high resolution mode:–12288 to
12287)
Analog output – 10 to 10V DC (External load
resistance 1 k Ω to 1 M Ω)
0 to 20 mA DC (External load
resistance 0 Ω to 600 Ω)
Analog output range Analog output rangeI/O characteristics
maximum resolution
0 to 5
V
1 to 5
V
– 10 to
10 V
Users
range
setting
0 to 20 m
A
4 to 20 m
A
Users
range
setting
Digital input
value
0 to 4000 – 4000 to 4000 0 to 4000 – 4000 to
4000
Normal
resolution
mode
Maximum
resolution
1.25 m
V
1.0 m
V
2.5mV 0.75m
V
5 μ A4 μ A 1.5 μ A
Digital input
value
0 to 12000 – 16000
to 16000
– 12000
to 12000
0 to 12000 – 12000
to 12000
High
resolution
mode
Maximum
resolution
0.416
mV
0.333
mV
0.625 m
V
0.333 m
V
1.66 μ A 1.33 μ A 0.83
μ
A
Ambient
tem
p
erature
25 ± 5 °C
Within ± 0.1 % (Voltage : ± 10mV, Current : ± 20μA)
Accuracy
(Accuracy in
respect to
maximum
analog output
value)
Ambient
tem
p
erature
0 to 55 °C
Within ± 0.3 % (Voltage : ± 30mV, Current : ± 60μA)
Conversion speed 80 μ s/ channel
Numbe
r
Name Description
1) RUN LED Displays the operating status of the D/A converter module.
On : Normal operation
Flashing : During offset/gain setting mode
Off : 5V power supply interrupted or watch dog timer error
2) ERROR LED Displays the error status of the D/A converter module.
On : Error
Off : Normal operation
Flashing : Error in switch settings
Switch No. 5 of the intelli
g
ent function module has been
set to a value other than "0".
3) External power supply
terminal
This is the terminal for connecting the 24 V DC external power
supply.
4) FG terminal Terminal for frame ground
4. Handling Precautions
(1) Do not drop the module or cause it to receive strong impact.
(2) Tighten the terminal screws for the module to the specified torque shown below.
Insufficient tightening torque could result in shorts, failures or malfunction.
Screw location Tightening torque
Module mounting screw (M3 screw) 0.36 to 0.48 N · m
Terminal block terminal screw (M3 screw) 0.42 to 0.58 N · m
Terminal block mounting screw (M3.5 screw) 0.66 to 0.89 N · m
FG terminal screw (M3 screw) 0.42 to 0.58 N · m
5. Wiring
5.1 Wiring precautions
(1) Use separate cables for the external output signal or external power supply
for the AC and D/A converter modules. Take steps to prevent the AC side
from being affected by surge or inductance.
(2) Ground one point of the shield for shielded wires or shielded cables.
Point
If it is difficult to wire FG terminals due to the limited installation space, use FG terminal L-shaped metal fitting.
5.2 External wiring
(1) Q68DAV
1 kW
1 MW
D/A
conversion
V+
COM
*1 *2
Motor drive module, etc.
GND
+24 V
A.G
+15 V
–15 V
A.G
DC/DC
converter
24V
24G
FG
24 V DC
Filter
to
Output range setting value can be set within the ranges described below
depending on the D/A converter module's model name.
y Q68DAV..........0H, 2H to 4H, FH
*1: The module activates at the analog output range within 1
to 5V, when 0H is set.
y Q68DAI...........0H, 1H, FH
*2: Switch 3 is set at decimal unit.
Setting is comparatively easier when the input type is change to decimal.
6. External Dimensions
8.5
(0.33)
2
(0.08)
27.4
(1.08)
90 (3.54)
98 (3.86)
unit
(
mm
(
in.
))
3.7
(0.15)
Q68DA
RUN
ERROR
IN 24VDC
FG
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
6.7
(0.26)
10.5
(0.41)
7.4
(0.29)
FG terminal L-shaped
metal fitting
FG terminal screw (M3 screw)
[DESIGN PRECAUTIONS]
CAUTION
Do not bunch the control wires or communication cables with the main circuit or power
wires, or install them close to each other.
They should be installed 100 mm (3.94 inch) or more from each other.
Not doing so could result in noise that may cause malfunction.
At power ON/OFF, voltage or current may instantaneously be output from the output
terminal of this module. In such case, wait until the analog output becomes stable to start
controlling the external device.
[INSTALLATION PRECAUTIONS]
CAUTION
Use the PLC in an environment that meets the general specifications given in the User's
Manual of the CPU module being used.
Using this PLC in an environment outside the range of the general specifications may cause
electric shock, fire, malfunction, and damage to or deterioration of the product.
While pressing the installation lever located at the bottom of module, insert the module fixing tab into
the fixing hole in the base unit until it stops.
Improper installation may result in malfunction , breakdown or the module coming loose and
dropping.
Securely fix the module with screws if it is subject to vibration during use.
Tighten the screws within the range of specified torque.
If the screws are loose, it may cause the module to fallout, short circuits, or malfunction.
If the screws are tightened too much, it may cause damage to the screw and/or the module,
resulting in fallout, short circuits or malfunction.
Be sure to shut off all phases of the external power supply used by the system before mounting or
removing the module.
Not doing so may cause damage to the module.
Do not directly touch the conductive area or electronic components of the module.
Doing so may cause malfunction or failure in the module.
[WIRING PRECAUTIONS]
CAUTION
Always ground the FG terminal for the PLC.
There is a risk of electric shock or malfunction.
When turning on the power and operating the module after wiring is completed, always attach
the terminal cover that comes with the product.
There is a risk of electric shock if the terminal cover is not attached.
Tighten the terminal screws within the range of specified torque.
If the terminal screws are loose, it may result in short circuits or malfunction.
If the terminal screws are tightened too much, it may cause damage to the screw and/or the
module, resulting in short circuits or malfunction.
Be careful not to let foreign matters such as sawdust or wire chips get inside the module.
These may cause fires, failure or malfunction.
The top surface of the module is covered with protective film to prevent foreign objects such as
cable offcuts from entering the module when wiring.
Do not remove this film until the wiring is complete.
Before operating the system, be sure to remove the film to provide adequate heat ventilation.
About This Manual
The following manuals are also related to this product. Order them if necessary.
Related Manual
Manual Name Manual No. (Model code)
D/A Converter Module User's Manual
SH-080054
(13JR02)
Type
Item
Q68DAV Q68DAI
Absolute maximum output ± 12 V 21 mA
Output short circuit protection Available
Insulation method Between I/O terminal and PLC power supply : Photocoupler insulation
Between output channels : Not insulated
Between external supply power and analog output : Not insulated
Number of occupied points 16 points
Connecting terminals 18 points terminal block
Applicable wire size 0.3 to 0.75 mm
2
Applicable solderless terminals Other terminals than FG:R1.25 - 3
(A solderless terminals with sleeves cannot be used)
FG terminal:R1.25-3, 1.25-YS3, RAV1.25-3, V1.25-YS3A
External supply power 24 V DC + 20 %, – 15 %
Ripple, spike within 500 mVP -P
Inrush current : 3.3A, within 70μs Inrush current : 3.1A, within 75μs
0.19 A 0.28 A
Internal current consumption
(5 V DC)
0.39 A 0.38 A
Weight 0.18 kg
3. Part Names
This section explains the names of the components for the D/A converter module.
Terminal Signal name
number
Q68DAV Q68DAI
1V+I+
2
CH.1
COM
CH.1
COM
3V+I+
4
CH.2
COM
CH.2
COM
5V+I+
6
CH.3
COM
CH.3
COM
7V+I+
8
CH.4
COM
CH.4
COM
9V+I+
10
CH.5
COM
CH.5
COM
11 V+ I+
12
CH.6
COM
CH.6
COM
13 V+ I+
14
CH.7
COM
CH.7
COM
15 V+ I+
16
CH.8
COM
CH.8
COM
17 24 V
18 24 G
1)
2)
3)
Q68DA
RUN
ERROR
IN 24VDC
FG
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
4)
(2) Q68DAI
0W
600W
D/A
conversion
I+
COM
*1 *2
Motor drive module, etc.
GND
+24V
A.G
+15V
–15V
A.G
DC/DC
converter
24V
24G
FG
24 V DC
Filter
to
*1 Use a twisted two core shielded wire for the power wire.
*2 If there is noise or ripples in the external wiring, connect a 0.1 to 0.47 m F25V
condenser between the V+/I+ terminal and COM.
5.3 Switch setting for intelligent functional module
The settings for the intelligent function module are performed using the I/O allocation
settings for the GX Developer. It can be easy to set by inputting using hexadecimal-4
digits.
Setting
Analog output range Output range setting value
4 to 20 mA 0 H *1
0 to 20 mA 1 H
Switch 1
Output range setting
(CH.1 to CH.4)
H
CH4 CH3CH2CH1
1 to 5 V 2 H
0 to 5 V 3 H
– 10 to 10 V 4 H
User range setting F H
Switch 2
Output range setting
(CH.5 to CH.8)
H
CH8 CH7CH6CH5
Switch 3 *2
CH8CH7CH6CH5CH4CH3CH2 CH1
b8 b7 b6 b5 b4 b3 b2 b1 b0
b15
to
00
HOLD/CLEAR function settin
g
0 : CLEAR
1 : HOLD
Switch 4
H
00
H
: Normal mode (non-synchronized)
01 to FF
H
: Synchronized output mode
0
H
:Normal resolution mode
1 to F
H
: High resolution mode
0
H
: Normal mode
(D/A conversion processing)
1 to F
H
: Offset/gain setting mode
Switch 5
0 : Fixed
Warranty
Mitsubishi Electric shall not be liable for any loss caused by reasons for which Mitsubishi is not held
accountable, lost business opportunities or unrealized gain on the customer's side resulting from failure of
the product, or any other damage, secondary disaster, accident, damage to equipment other than the
product or disruption of other business operations arising out of special circumstances which may or may
not have been predicted at Mitsubishi.
For safe use of the product
z This product is manufactured as a general-purpose product intended for general industrial use only. It is
not designed nor manufactured for use in an equipment or system affecting human lives.
z If you are considering to use this product in equipment or systems for nuclear power generation, power
generation, aerospace, medical or passenger transport applications, consult our sales representatives.
z This product is manufactured under our strict quality control system. However, if the product is used in
the intended facility in such a way that a failure of the product may lead to serious accident or loss,
incorporate backup or fail-safe functions into the system design.
U.S.A Mitsubishi Electric Automation Inc.
500 Corporate Woods Parkway Vernon
Hills, IL 60061
Tel : +1-847-478-2100
Brazil MELCO-TEC Rep. Com.e Assessoria
Tecnica Ltda.
Rua Correia Dias, 184,
Edificio Paraiso Trade Center-8 andar
Paraiso, Sao Paulo, SP Brazil
Tel : +55-11-5908-8331
Germany Mitsubishi Electric Europe B.V. German
Branch
Gothaer Strasse 8 D-40880 Ratingen,
GERMANY
Tel : +49-2102-486-0
U.K Mitsubishi Electric Europe B.V. UK
Branch
Travellers Lane, Hatfield, Herts., AL10
8XB,UK
Tel : +44-1707-276100
Italy Mitsubishi Electric Europe B.V. Italian
Branch
Centro Dir. Colleoni, Pal. Perseo-Ingr.2
Via Paracelso 12, 20041 Agrate B.,
Milano, Italy
Tel : +39-039-6053344
Spain Mitsubishi Electric Europe B.V. Spanish
Branch
Carretera de Rubi 76-80
08190 Sant Cugat del Valles,
Barcelona, Spain
Tel : +34-93-565-3131
France Mitsubishi Electric Europe B.V. French
Branch
25 Boulevard des Bouvets, F-92741
Nanterre Cedex, France
TEL: +33-1-5568-5568
South Africa Circuit Breaker Industries LTD.
Tripswitch Drive, Elandsfontein Gauteng,
South Africa
Tel : +27-11-928-2000
Hong Kong Ryoden Automation Ltd.
10th Floor, Manulife Tower, 169 Electric
Road, North Point, HongKong
Tel : +852-2887-8870
China Ryoden Automation Shanghai Ltd.
3F Block5 Building Automation
Instrumentation Plaza 103 Cao Bao Rd.
Shanghai 200233 China
Tel : +86-21-6120-0808
Taiwan Setsuyo Enterprise Co., Ltd.
6F., No.105 Wu-Kung 3rd.RD, Wu-Ku
Hsiang, Taipei Hsine, Taiwan
Tel : +886-2-2299-2499
Korea HAN NEUNG TECHNO CO.,LTD.
1F Dong Seo Game Channel Bldg.,
660-11, Deungchon-dong Kangsec-ku,
Seoul, Korea
Tel : +82-2-3660-9552
Singapore Mitsubishi Electric Asia Pte, Ltd.
307 Alexandra Road #05-01/02,
Mitsubishi Electric Building
Singapore 159943
Tel : +65-6473-2308
Thailand F. A. Tech Co.,Ltd.
898/28,29,30 S.V.City Building,Office
Tower 2,Floor 17-18 Rama 3 Road,
Bangkpongpang, Yannawa,
Bangkok 10120
Tel : +66-2-682-6522
Indonesia P.T. Autoteknindo SUMBER MAKMUR
Jl. Muara Karang Selatan Block a Utara
No.1 Kav. No.11 Kawasan Industri/
Pergudangan Jakarta - Utara 14440
Tel : +62-21-663-0833
India Messung Systems Put,Ltd.
Electronic Sadan NO:111 Unit No15,
M.I.D.C BHOSARI,PUNE-411026, India
Tel : +91-20-712-2807
Australia Mitsubishi Electric Australia Pty. Ltd.
348 Victoria Road, PostalBag, No 2,
Rydalmere, N.S.W 2116, Australia
Tel : +61-2-9684-7777
Country/Region Sales office/Tel
When exported from Japan, this manual does not require application to the Ministry
of Economy, Trade and Industry for service transaction permission.
Specifications subject to change without notice.