A SERVICE OF

logo

MECHANICAL INSTALLATION (CONTINUED)
DUCTING (CONTINUED)
RETURN: FROM LIVING SPACE TO ERV
•Staleairfromthehouseshouldbeexhaustedfromoneexhaustgrillecentrallylocated,suchasahallway.Formulti-floorhomes,theexhaust
grille should be located on the same floor as the kitchen.
•Tokeepthecorefreeofgrease,theERVductworkmustnotbeconnectedtoakitchenexhaustfanduct.
•TheERVductworkshouldremainseparatefrombathroomexhaustfanducts.
•6”round,galvanizedductworkrecommended.Ifrectangular
duct is used, it must have an equivalent air flow rating.
•Asoundabsorberatleast6ft.long,consistingof1”thickrigid
fiberglass duct or insulated flexible duct is recommended for
maximum absorbing of air movement sounds between the unit
and the living space return grille.
1. Install a balancing damper in the duct near the ERV.
(See Figure 15.)
2. Complete the Return ducting.
SUPPLY: FRESH AIR FROM ERV TO HOUSE
•Itisrecommendedthatthesupplyductbeconnecteddirectlyto
the HVAC return duct, a minimum of 10’ from the HVAC blower.
•6”round,galvanizedductworkisrecommended.
1. Install a balancing damper in the duct near the ERV.
(See Figure 16.)
2. Complete the Supply ducting. Using a collar for the duct
connection to the HVAC return duct is recommended.
OUTDOOR: EXHAUST AND FRESH AIR CONNECTIONS
•InsulatedductofatleastR-4insulatingvaluewithacontinuousvaporbarriermustbeusedforbothductrunsconnectingtheERVtothe
outdoors. The vapor barrier must be sealed at both ends and extend from the ERV housing to the outer wall. (See Figure 17.)
DAMPER
DAMPER
FIGURE 16 – Damper in ERV Supply
90-1753
DAMPER
FIGURE 15 – Damper in ERV Return
90-1747
INSULATED DUCT
BUTTERFLY DAMPER
(IF ERV NOT RUNNING CONTINUOUSLY)
FRESH AIR
FROM OUTSIDE
STALE AIR
TO OUTSIDE
FIGURE 17 – Ducting to Outdoors
90-1747
7