SECTION 4 ADJUSTMENTS
4-- 1
Time Delay Adjustment
Standard time delays are set to customer specifications
(if none specified, standard factory settings are used).
To change a setting, follow procedure on page 4-2. Use
Table 4-1 as a guide to time delay values and their corre-
sponding adjustment DIP switch or potentiometer.
Table4-1.TimeDelaySettings
DESCRIPTION LABELS
FACTORY
SETTING
ADJUSTMENT
RANGE
S3 DIP
SWITCH
ADJUSTMENT
POTENTIOMETER
Override Momentar
1second Actuator 1 on
1
Normal Source Outages
3secon
s
3seconds Actuator 1 off
1
TIMER 0 minutes 0to5
rans
er to
mergency
N
E
(full ccw)
minutes
—
2
Override Momentary
Emergency S. Outages
— 4seconds non-adjustable — — —
TIMER 30 minutes 1secondto
etrans
er to
orma
E
N
(full cw)
30 minutes
—
1
Unloaded Running
(Engine Cooldown)
— 5 minutes non-adjustable — — —
Sensor Adjustments
Voltage and f requency sensor pickup and dropout
points are set to customer specifications (if none
specified, standard factory settings are used). To change
a setting, follow procedure on page 4–2. Use Tables 4-2
and 4–3 for se ttings and corresponding DIP switch
actuators.
NOTICE
Any change in these settings may affect the
normal operation of the automatic transfer
switching equipment. This change could allow
the load circuits to remain connected to a low
voltage source.
Ta ble 4-2. Voltage and Frequency Settings. ( Shaded DIP switches are standard factory settings).
%ofnominal
S1 DIP
FACT . SET ADJ RANGE
SWITCH
95 % * Actuator 3 off
3
c
up 90 %
90 % Actuator 3 on
3
90 % *
Actuator 1 off
Actuator 2 off
21
Normal Source Voltage
85 %
Actuator 1 on
Actuator 2 off
21
DO
N Dropout
85 %
80 %
Actuator 1 off
Actuator 2 on
21
70 %
Actuator 1 on
Actuator 2 on
21
Emer
enc
Source Volt-
–– Pickup 90 % non-adjustable
age
–– Dropout 75 % non-adjustable
––
–– Pickup 95 % non-adjustable
–– Dropout 85 % non-adjustable
––
Emergency Source
Frequency
60
50
60 Hz Actuator 4 off
4
Hz
60
50
z 60
z
50 Hz Actuator 4 on
4
3phase Actuator 6 off
6
o
tage
ases 3 4 ,14 3 4
1 4 3 4
1phase Actuator 6 on
6
* If dropout voltage is set to 90%, the pickup voltage must be set to 95%.
Table 4-3. Transformer Voltage Adjust.
(Low setting shifts all voltage settings down 4.2%; for example, 240 V to 230 V, or 480 V to 460 V)
DESCRIPTION LABELS FACTORY SETTING ADJUSTMENT S3 DIP SWITCH
OW
LOW Actuator 2 off
2
o
tage
ust
4.2%
HI
HI Actuator 2 on
2