Mounting/Dismounting Modules Excel 800
EN1B-0410GE51 R0908A
18
Connecting Laptops (XL-Online/CARE)
► Connect a laptop (on which e.g., XL-Online or CARE has
been installed) to the HMI interface or L
ONWORKS interface
of the XCL8010AU
Controller Module by means of
– the XW885 cable or
– the XW585 cable connected with an XW586 Cable.
XCL8010AU Terminals
74
14
10 7
2
3
4
78
73
13
9 6
1
77
72
12
8 5
76
71
11
75
24
V~
24
V~
24
V~
24
V~ 0
LON
2
C- C-
C+ C+
LON
2
LON
1
LON
1
24
V~ 0
24
V~ 0
NC
24
V~0
COM
B
COM
B
COM
A
COM
A
SHIELD SHIELD
87 6
5
4 32 1
*
*Watch Dog
Relay
Fig. 26. Terminal assignment and internal connections of
the XCL8010AU Controller Module
Table 12. Description of XCL8010AU terminals
ter-
minal
signal comment
71, 75 COM a
2-wire communication bus
(LON/Panel Bus)
72, 76 COM b
2-wire communication bus
(LON/Panel Bus)
73, 77 24 V~ Power supply for I/O modules
74, 78 24 V~0 Power supply for I/O modules
1 24 V~ Power supply from transformer
2 24 V~0 Power supply from transformer
3 24 V~0 Alarm/watchdog output
4 NC Alarm/watchdog output
5, 8 C+ C-Bus
6, 9 C- C-Bus
7, 10 Shield C-Bus shield
11, 12 LON LONWORKS IN
13, 14 LON LONWORKS OUT
Features
LONWORKS Interface and Terminals
The XCL8010AU Controller Module features
• An RJ45 socket serving as an interface
to connect laptops or HMIs to the L
ONWORKS Bus
• LONWORKS terminals 11, 12, 13, and 14
to connect L
ONWORKS Bus I/O modules or other
L
ONWORKS devices to the XCL8010AU Controller or other
L
ONWORKS controllers.
Fig. 27. L
ONWORKS interface and LONWORKS terminals
LONWORKS Interface Signals on RJ45 Socket
Table 13. Signals of L
ONWORKS interface
pin signal type
1 Connection to LONWORKS Bus
2 Connection to LONWORKS Bus
3 ─ 8 Not used
LONWORKS Service LED and Button
The XCL8010AU Controller Module is equipped with a
L
ONWORKS service button and corresponding LONWORKS
Service LED (status: yellow/OFF).
1
LON
2
Fig. 28. L
ONWORKS service button (1) and service LED (2)
See also section "Troubleshooting" on page 31.