4 CONFIGURATION MODE…
Fig. 4.3 Hardware Configuration and Input/Output Ranges
50Hz/60Hz Relay 1 Relay 2* Relay 3* Logic O/P Analog O/P
Source Source Source Source Source
1 A Alarm 1 Alarm 2 Alarm 3 TCP** PV
2 b Alarm 1 Alarm 2 Alarm 3 TWP** PV
3 C TCP** Alarm 1 Alarm 2 TWP** PV
4 D TWP** Alarm 1 Alarm 2 TCP** PV
5 E Alarm 1 Alarm 2 Alarm 3 TCP** PV Average
U Custom Custom Custom Custom Custom
A 1KC0
A – Hardware Configuration
TCP = Totalizer Count Pulse TWP = Totalizer Wrap Pulse PV = Process Variable
b 1KC0
B – Input Type and Range Configuration
C 1KC0
D – Process Variable
Display Decimal Places
Display
0 xxxx
1 xxx . x
2 xx . xx
3 x . xxx
4 x . xxxx
d 1KC0
C – Temperature Units
Display Temperature Units
C Degrees C*
F Degrees F*
0 No temperature units
* Temperature inputs only
Display
b T/C Type B
E T/C Type E
J T/C Type J
K T/C Type K
n T/C Type N
r T/C Type R
S T/C Type D
t T/C Type T
P PT100 RTD
Display
1 0 to 20 mA
2 4 to 20 mA
3 0 to 5 V
4 1 to 5 V
6 0 to 50 mV
7 4 to 20 mA (square root lineariser)
U Custom Configuration
* Only available if the appropriate option board is fitted.
** Pulse energizes assigned relay