77
Operation Selection Function Parameters
3
INVERTER FUNCTIONS
Relationships between Pr. 79 and Pr. 340
Pr. 340
Setting
Pr. 79
Setting
Operation Mode at
Power On or Power
Restoration
Remarks
0
(Factory
setting)
0 External operation mode
Can be switched to the CC-Link operation
mode by CC-Link communication.
1 PU operation mode Operation mode cannot be switched.
2 External operation mode
Can be switched to the CC-Link operation
mode by CC-Link communication.
3
External/PU combined
operation mode
Operation mode cannot be switched.
4
External/PU combined
operation mode
1
0 CC-Link operation mode
Can be switched to the external operation
mode by CC-Link communication.
1 PU operation mode Operation mode cannot be switched.
2 CC-Link operation mode
Can be switched to the external operation
mode by CC-Link communication.
3
External/PU combined
operation mode
Operation mode cannot be switched.
4
External/PU combined
operation mode