![](https://pdfstore-manualsonline.prod.a.ki/pdfasset/8/48/8486f188-e710-4ef0-8443-7229c6c9810f/8486f188-e710-4ef0-8443-7229c6c9810f-bg12.png)
18
FPΣ (Sigma)
Specification tables
GG EE NN EE RR AA LL SS PP EE CC II FF II CC AATT II OO NN SS
Rated operating voltage 24VDC
Operating voltage range 21.6 to 26.4VDC
Allowable no voltage time 4ms (at 21.6V), 10ms (at 26.4V)
Ambient temperature 0°C to +55°C
Storage temperature -20°C to +70°C
Ambient humidity 30 to 85% RH (Non-condensing)
Storage humidity 30 to 85% RH (Non-condensing)
Vibration resistance 10 to 55Hz, 1 cycle/min.,
double amplitude of 0.75mm,
10min. on 3 axes
Shock resistance 98m/s
2
or more,
4 times on 3 axes
Noise humidity 1,000V (p-p)
with pulse
widths 50ns and 1µs
Operating condition free from corrosive gasses
and excessive dust
II NN PP UU TT SS PP EE CC II FF II CC AATT II OO NN SS
Insulation method Optical coupler
Rated input voltage 24VDC
Input voltage range 21.6 to 26.4VDC
Rated input current 3.5mA - 8mA depends on input no.
8 points/common (FPG-C24), 16 points/common (FPG-C32/C28),
32 points/common (FPG-XY64). Either the positive or
negative of input power supply can be connected to terminal
Min. ON voltage / Max. OFF current 19.2V / 3mA - 6mA depends on input no.
Max. ON voltage / Min. OFF current 2.4V / 1.3mA
Input impedance 3k - 6.8k depends on input no.
Response time CPU: 1ms or less, 5µs (HSC, pulse catch, interrupt input)
Expansion: 0.2ms (OFF -> ON)
0.3ms (ON -> OFF)
Operating indicator LED
OO UU TT PP UU TT SS PP EE CC II FF II CC AATT II OO NN SS -- TT RR AA NN SS II SS TT OO RR OO UU TT PP UU TT TT YY PP EE
Item FPG-C32 (NPN) FPG-C28 (PNP)
Insulation method Optical coupler
Output method Open collector
Rated voltage range 5 to 24VDC 24VDC
Operating load voltage range 4.75 to 26.4VDC 21.6 to 26.4VDC
For Y0, Y1, Y3, Y4: 0.3A For Y0, Y1, Y3, Y4: 0.5A
For Y2, Y5 to YF: 0.1A For Y2, Y5 to YB: 0.3A
For Y0, Y1, Y3, Y4: 0.9A For Y0, Y1, Y3, Y4: 1.5A
For Y2, Y5 to YF: 0.5A For Y2, Y5 to YB: 0.7A
Output points per common 16 points/common 12 points/common
For Y0, Y1, Y3, Y4 at 15mA or lesss: <2µs
For Y2, Y5 and higher: < 0.2ms
For Y0, Y1, Y3, Y4 at 15mA or lesss: <8µs
For Y2, Y5 and higher: < 0.5ms
Power supply for driving internal circuit none
Operating indicator LED
Phase fault protection Thermal protection for Y2, Y5 and higher
Response time
OFF -> ON
ON -> OFF
Max. load current
Max. surge current
OO UU TT PP UU TT SS PP EE CC II FF II CC AATT II OO NN SS -- RR EE LL AAYY OO UU TT PP UU TT TT YY PP EE
Output type Normally open (1 Form A)
Rated control capacity 2A 250VAC, 2A 30VDC (max. 4.5A/common)(resistive load)
Output points per common 8 points/ common
10ms or less
8ms or less
Mechanical life time 20 million operations or more
Electrical life time 100.000 operations or more
Surge absorber 21.6 to 26.4VDC (70mA)
Operating indicator LED
OFF -> ON
ON -> OFF
Response time
Input points per common
20060227_FP_Sigma.qxd 15.02.2006 14:55 Uhr Seite 18