4.2 Control Circuit and External Battery Interface Connections
The following illustrates the wiring connections of the Control Circuits and Battery Interface
Circuits.
4.1.4 Recommended Wire Size and Tightening Torque UPS Control and Battery Interface
Minimum Wire Size and Tightening Torque for UPS Control and Battery Interface Circuits
USE MINIMUM 75° C COPPER WIRING
TERMINAL (TERMINAL #) AWG TIGHTENING TORQUE
*UPS CONTROL CIRCUITS (1-18) 14-16 8 in-lbs.
*BATTERY CONTROL CIRCUITS (3-6) 14-16 8 in-lbs.
*Indicates Class 1 wiring method is to be used.
24 4200FA User’s Manual