JKSSS+ Series - 58
JKSSS+ Series 2.3 - 4.2KV
SP.6UserI/OConguration(SetpointPage6)
(SecurityLevel:2)
: The
controller provides up to 4 digital external inputs
which are individually programmable. A description
name can be assigned to each individual input for
easy identication.
• Factory programmed for TCB
Trip.
If used, this setpoint must be
enabled.
The user can assign a
description name to the input to easily identify
the cause of external trip or alarm. Up to 15
characters including spaces can be used to assign
the name.
The external input can
be set as either a normally open or normally
closed contact.
Upon a change in
contact setting, the unit will wait the programmed
amount of time before generating an output. If
no delay is needed, then input 0 seconds. The
controller will post an event upon seeing a change
in state.
: The setup screens and
setpoints for External Input #3 includes the option
of being congured for Dual Ramp. In Dual Ramp
mode, the initial contact setting is the same as the
START RAMP #1. Upon a change in input contact
state, the controller will switch over to START
RAMP #2 and use that setting for start control
mode. Note: The start RAMP types should only be
switched while the motor is stopped. In Setpoint
Page 4 Relay Assignments, do not assign any
output relay to this function. The controller will
ship with External input #3 programmed for dual
ramp. If it is not needed, disable the dual ramp.
: This input screens are for the
thermostat input and can be enabled or disabled.
Note: It is recommended that this function remain
enabled. If the thermostat indicates an over
temperature condition, the controller will trip the
motor.
USER
PROGRAMMABLE
EXTERNAL
INPUTS
(Continued)
TCB FAULT
SELECT: ENABLED
NAME EXT. INPUT #1
TCB FAULT
Options: Enabled or Disabled See text for directions
EXTERNAL INPUT #2
SELECT: DISABLED
NAME EXT INPUT #2
Options: Enabled or Disabled See text for directions
DUAL RAMP
SELECT: DUAL RAMP
NAME EXT INPUT #3
SECOND RAMP
Options: Enabled, Disabled or
Dual Ramp
See text for directions
THERMOSTAT
SELECT: ENABLED
NAME EXT INPUT #4
THERMOSTAT
Options: Enabled or Disabled See text for directions
TCB FAULT
TYPE: NORMALLY OPEN
Options: Normally Open or
Normally Closed
EXTERNAL INPUT #2
TYPE: NORMALLY OPEN
Options: Normally Open or
Normally Closed
DUAL RAMP
TYPE: NORMALLY OPEN
Options: Normally Open or
Normally Closed
THERMOSTAT
TYPE: NORMALLY CLOSED
Options: Normally Open or
Normally Closed
TCB FAULT
TIME DELAY: 1 SEC.
Range: 0 - 60 SEC
Increments of 1
EXTERNAL INPUT #2
TIME DELAY: 0 SEC.
Range: 0 - 60 SEC.
Increments of 1
DUAL RAMP
TIME DELAY: 0 SEC.
Range: 0 - 60 SEC
Increments of 1
THERMOSTAT
TIME DELAY: 1 SEC.
Range: 0 - 60 SEC.
Increments of 1