Controls
31RT-SVX19A-E4
Control wiring
The control circuit is 24 V AC. Unit
includes a 400/24 V transformer.
WARNING!The unit disconnect
switch must be opened and locked
open. Risk of injury and
electrocution.
CAUTION!The unit 24 V transformer
must not be used to power
accessories mounted on site, other
than those proposed by Trane.
Unit controlled by thermostat
Figure 11 - Thermostat wiring
Trane THS01,THS02, THP01 and
THP02 Thermostats are directly
connected to RTRM board
(J7 connector). TRANE THS02 and
THP03 thermostats are directly
connected to RTRM board
(J6 connector).
Install the electrical link between the
thermostat (thermostat terminal
strip) and the unit (J6 or J7
connector) in compliance with the
interconnection diagram. The low
voltage wiring must not be laid in
the same pipes as the power cables.
The sizes and lengths of the
thermostat connection wires are
given in Table 29. The total
resistance of these control cables
must not exceed 5 ohms. If the
resistance exceeds this value the
thermostat may not operate with
the same precision.
Table 29 - Zone sensor wire size and
maximum length
Maximum length
Zone sensor wire size
Wire
size
(mm²)
Maximum
wire lengh
(m)
THS/THP 03
0.33 45
0.5 76
0.75 115
1. 3 185
2 300
Conventionnal
thermostat
THS/THP 01-02
0.33 10
0.5 15
0.75 23
1. 3 37
2 60