External Control and Alarms
Features
An external control and alarm circuit card is located behind the shelf’s top front access panel. This circuit
card provides three sets of Form C relay contacts for external alarms, plus an ESTOP input. A terminal
block is provided on the circuit card for customer connections.
Restrictions
Terminal block wire size capacity is 14 to 26 AWG.
Relay contacts are rated for 1A at 30VDC or 0.3A at 60VDC.
Relays are energized for normal operating conditions and de-energized for an alarm condition.
Ordering Notes
1) Recommended Wire Size: 22 AWG for Loop Lengths Up to 200 ft.
18-20 AWG for Loop Lengths Over 200 ft.