Honeywell PUB4024S Universal Remote User Manual


 
SPYDER® BACNET® PROGRAMMABLE CONTROLLERS
63-2689—05 12
Table 7. Description of wiring terminal connections for
PUB6438S, PVB6436AS, and PVB6438NS.
IMPORTANT
If the controller is not connected to a good earth
ground, the controller's internal transient protection
circuitry is compromised and the function of protect-
ing the controller from noise and power line spikes
cannot be fulfilled. This could result in a damaged cir-
cuit board and require replacement of the controller.
Refer to installation diagrams for specific wiring.
All controllers have the terminal arrangements similar to the
examples shown in Fig. 15 as described in Table Table 7 on
page 12.
MS/TP MAC ADDRESS DIP SWITCHES
The MS/TP MAC address DIP switches are used to set the
unit's MAC address. Each Spyder BACnet on an MS/TP
network must have a unique MAC address in the range of 0-
127 (address 0 should be avoided as it is the Honeywell factory
default MAC address for all MS/TP devices).
MS/TP SERVICE CONNECTOR PINS
Local device MS/TP network connection is provided via the
molex connector pins (0.100-in. molex connector—part
number: 22-01-2035).
Fig. 15. Controller Terminal Connections, MS/TP MAC
address DIP switches, MS/TP service connector pins, and
BACnet Status LED for the PUB's and PVB's (PVB6438NS
shown).
Wiring Applications (Examples)
Fig. 16–Fig. 22, beginning on page 13, illustrate controller
wiring for the following configurations.
Typical controller wiring for VAV application using the TR23
Wall Module and a C7770A Air Temperature Sensor (see
Fig. 16 on page 13).
Typical controller wiring for VAV application with staged
reheat (see Fig. 17 on page 14).
Typical controller wiring for PWM reheat and PWM
peripheral heat valve actuator (see Fig. 18 on page 15).
Typical controller wiring for AHU application (see Fig. 19 on
page 16).
Typical controller wiring for 4 to 20 mA enthalpy sensors and
digital inputs (see Fig. 20 on page 17).
Terminal Label Connection
INPUT POWER & GROUND
1 24 Vac 24 Vac Power
2 24 Vac COM 24 Vac Power
3 EGND Earth Ground
4 SHLD MS/TP Shield
5SBUS 1 Sylk
6SBUS 2 Sylk
NETWORK CONNECTIONS
7BAC + LONWORKS® communications
8BAC - LONWORKS® communications
DIGITAL OUTPUTS
a
9 DO-1 Digital Output
10 DO-2 Digital Output
11 COM Common
12 DO-3 Digital Output
13 DO-4 Digital Output
14 COM Common
15 DO-5 Digital Output
16 DO-6 Digital Output
17 COM Common
18 DO-7 Digital Output
19 DO-8 Digital Output
20 COM Common
ANALOG OUTPUTS
b
21 AO-1 Analog Output
22 COM Common
23 AO-2 Analog Output
24 AO-3 Analog Output
25 COM Common
DIGITAL INPUTS
c
26 DI-1 Digital Input
27 DI-2 Digital Input
28 COM Common
29 DI-3 Digital Input
30 DI-4 Digital Input
ATTACHED DEVICE(S) POWER
31 20 Vdc 20 Vdc Power
UNIVERSAL INPUTS
32 UI-1 Universal Input
33 COM Common
34 UI-2 Universal Input
35 UI-3 Universal Input
36 COM Common
37 UI-4 Universal Input
38 UI-5 Universal Input
39 COM Common
40 UI-6 Universal Input
a
For the PVB6436AS controller ONLY, terminals 18, 19, and 20 (DO7,
DO8, & COM) are not present. The actuator is internally hardwired to
these terminals.
b
Analog outputs may be configured as digital outputs and operate as fol-
lows:
– False (0%) produces 0 Vdc, (0 mA)
– True (100%) produces the maximum 11 Vdc (22 mA)
c
Digital inputs: Open circuit = False; Closed circuit = True
BACnet MS/TP MAC
A
DDRESS DIP SWITCHES
TERMINALS 1-8
TERMINALS 9-20
TERMINALS 21-40
AO-1
COM
AO-2
AO-3
COM
UI-1
COM
UI-2
UI-3
COM
UI-4
UI-5
COM
UI-6
DI-1
DI-2
COM
DI-3
20V DC
DI-4
NET-2
NET-1
SHLD
EGND
24 VAC
24VAC COM
DO-1
COM
DO-2
DO-3
DO-4
DO-5
COM
DO-6
COM
1
2
3 4 5 6
7 8
1 0 9 2 3 4 5 6 7 8 0 9
1 1 1 1 1 1 1 1 1 2 1
1
2
3 4
5
6
7 8
0
9
2
2 2
2 2
2
2
2 2
3
3
1
2
3 4
5
6
7 8
0
9
3
3
3
3 3
3 3
3 4
M29332
DO-7
DO-8
COM
SBUS1
SBUS2
LOCAL BACnet MS/TP
MOLEX CONNECTOR PINS