Mitsubishi Electronics LY41NT1P Universal Remote User Manual


 
64
6.2.2 For the 40-pin connector type module
(1) Precautions
Use copper wires having temperature rating of 75°C or more for the connectors.
Tighten the connector screws within the following specified torque range.
(2) Applicable connectors
The 40-pin connector for input module, output module, or I/O combined module is obtained by user.
The following tables list the 40-pin connectors, crimp tool, and pressure-displacement tools.
(a) 40-pin connector
*1 Use cables with outside diameter of 1.3mm or shorter to connect 40 cables to the connector.
In addition, consider the amount of current to be used and select appropriate cables.
(b) Crimp tool and pressure-displacement tools for the 40-pin connectors
For wiring of connector and usage of crimp tool and pressure-displacement tool, contact FUJITSU
COMPONENT LIMITED.
Screw type Tightening torque range
Connector screw (M2.6) 0.20 to 0.29Nm
Type Model Name Applicable wire size Applicable models
Soldering connector
(straight out type)
A6CON1
*1
0.08 to 0.3mm
2
(28 to 22 AWG) (stranded wire)
LX41C4, LX42C4, LY41NT1P, LY42NT1P,
LY41PT1P, LY42PT1P, LH42C4NT1P,
LH42C4PT1P
Crimp connector
(straight out type)
A6CON2
0.088 to 0.24mm
2
(28 to 24 AWG) (stranded
wire)
Pressure-displacement connector
(straight out type)
A6CON3
28 AWG (stranded wire)
30 AWG (single wire)
Flat cable of 1.27mm pitch
Soldering connector
(both for straight out and 45-degree
types)
A6CON4
*1
0.088 to 0.3mm
2
(28 to 22 AWG) (stranded
wire)
Type Model name Contact
Crimp tool FCN-363T-T005/H
FUJITSU COMPONENT LIMITED
Pressure-
displacement tool
FCN-367T-T012/H (locator plate)
FCN-707T-T001/H (cable cutter)
FCN-707T-T101/H (hand press)