FX1S Series Programmable Controllers Outputs 6
6-8
6.3.1 Response Times
OFF times increase as the load current decreases.
For improved response times use a 'dummy' resistor, see Figure 6.4. If a response time of 0.5
ms or better is required when using 'light loads' use a 'dummy' resistor and ensure the signal
line has a current greater than 60mA/24V DC.
Figure 6.4: Dummy load
Y000 and Y001 are high speed response outputs with
the following characteristics:
10 - 100 mA at 5 - 24V DC, 100 kHz maximum output
signal.
If the high speed response is required, a current of 10 -
100mA must be used.
5 to 24V
Y
+V
Dummy load Load