Orion Car Audio OE331-21 Universal Remote User Manual


 
4
Analog Input
Configurations
The first five analog inputs and input #7 can be configured in several different ways.
Input #6 can be used for Static Pressure and accepts the standard pressure sensor with the
phone jack connector, available from WattMaster Controls.
The following configurations are available:
1. Thermister Type III Temperature Sensors (Scaled for Fahrenheit)
2. Thermister Type III Temperature Sensors (Scaled for Celsius)
3. 4 – 20ma User Scaled
4. 0 – 5 vdc User Scaled
5. Wall Sensor Slide Offset
6. Binary Contact Closure
7. Read Global Analog Broadcast from another Controller