Raypak Y-200 Series Universal Remote User Manual


 
4-20 mA / 2-10 VDC Input Control Module Installation and Operating Manual
Installation
1. Verify that the control signal is within the 4-20
mA / 2-10 VDC parameter.
2. Turn off the power to the Y-200.
3. Open the front cover of the Y-200 to access the
display/keypad door.
4. Open the display/keypad door to access the
Y-200 Control Board (P/N 601670).
5. Secure the nylon standoff (P/N 550767) onto
the Y-200 Control Board.
6. Plug the 4-20 mA / 2-10 VDC Module into the
Y-200 Control Board at the J20 expansion port
(10-pin plug), securing Module with nylon
standoff.
7. Attach 4-20 mA / 2-10 VDC signal wires to
2-pin plug connector (P/N 650935).
8. Plug 2-pin connector into either the J1 or J2 con-
nection of Module (J1 for 4-20 mA operation, J2
for 2-10 VDC operation).
4-20 mA /2-10 VDC Module
(P/N 601740)
Nylon stand-off (P/N 550767)
Hole for nylon
stand-off
Y-200 Control Board (P/N 601670)
2-pin plug connector (P/N 650935)
2