16 ACS 3216 Operators Manual
nor
Normal
4.SENS SENSE To configure the polarity of
output channel 4
Inv
Inverted
nor
Conf
LOGIC INPUT LIST ‘la’ / ‘LB
Name Scrolling Display Parameter Description Value Default Access Level
L.TYPE LOGIC INPUT
TYPE
Input channel type
L.IP
Logic input As order
code
Conf
Read only
none
Input not used
Ac.AL
Alarm acknowledge
SP2
Setpoint 2 select
Loc.b
Front keypad disable
t.res
Timer/programmer reset
t.run
Timer/programmer run
t.rrS
Timer/programmer run/reset. Make to
run, break to reset
t.HLd
Timer/programmer hold
Man
Manual status
Sby
Standby mode. In this mode control
outputs go to zero demand
rmt
To allow a remote setpoint to be
selected through the LA digital input.
rec
Recipe select through IO1 digital
input
UP
Remote key ‘Up’
L.d.in LOGIC INPUT
FUNCTION
To configure the function of the
digital input
dwn
Remote key ‘Down’
Ac.AL
Conf
nor
Normal
Inv
Inverted
L.SENS LOGIC INPUT
SENSE
To configure the polarity of the
input channel
4.20
4-20mA output
nor
Conf
SETPOINT LIST ‘SP
Name Scrolling Display Parameter Description Value Default Access Level
SP1
Setpoint 1 selected
SP.SEL SETPOINT
SELECT
This enables the main or secondary
setpoint to be selected form the front
panel buttons
SP2
Setpoint 2 selected
SP1
L3
SP1 SETPOINT 1 Main or normally selected setpoint Low to high setpoint limits
0
L3
SP2 SETPOINT 2 Secondary or standby setpoint Low to high setpoint limits
0
L3
SP.HI SETPOINT HIGH
LIMIT
Maximum allowable setpoint setting Setpoint low limit (SP.LO) to high range
limit. Also limited by the rng.hi and
rng.lo parameters
Range
High Limit
L3
SP.LO SETPOINT LOW
LIMIT
Minimum allowable setpoint setting Low range limit to Setpoint high limit
(SP.HI). Also limited by the rng.hi and
rng.lo parameters
Range
Low Limit
L3
rEm.sp REMOTE
SETPOINT
Reads the current remote setpoint value
when remote setpoint is in use
Read only
No
Not selected
l-r REMOTE
SETPOINT
SELECT
To select the remote digital
communications setpoint
YES
Selected
no
Conf
SP.RAT SETPOINT RATE
LIMIT
Limits the rate of change of the setpoint.
Operates on both SP1 and SP2
Step change (OFF) or 0.1 to 3000
display units per minute.
Resolution one decimal place more than
PV
Off
L3
min
Minutes
Hour
Hours
rampu SETPOINT RAMP
UNITS
To set the units for the setpoint rate limit
SEC
Seconds
min
L3
loc.t LOCAL SETPOINT
TRIM
To apply a fixed offset to the setpoint in
use
-199.9 to 300.0
0.0
L3
REM.HI REMOTE INPUT
HIGH SCALAR
Sets the maximum scale limit for the
remote setpoint
REM.lo REMOTE INPUT
LOW SCALAR
Seta the minimum scale limit for the
remote setpoint
Between Range High and Low Limits L3