ALARM, HIGH TEMPERATURE
BIT#:
4
DESCRIPTION:
This status bit states the temperature controller has exceeded its over setpoint deviation. This assumes the
3200 has been set up such that the first configured alarm (e.g. Alarm 2 if Alarm 1 is not configured) is a high
alarm.
ALARM, LOW TEMPERATURE
BIT#:
5
DESCRIPTION:
This status bit states the temperature controller has exceeded its below setpoint deviation. This assumes the
3200 has been set up such that the second configured alarm (e.g. Alarm 3 if Alarm 1 is not configured and
Alarm 2 is a high alarm) is a low alarm.
STATUS, MACHINE 1
POLL:
20 42
SELECT:
N/A
FORMAT:
16 Bits
UNITS:
None
DESCRIPTION:
Identical to definition of STATUS, PROCESS above
STATUS, MACHINE 2
POLL:
20 44
SELECT:
N/A
FORMAT:
16 Bits
UNITS:
None
DESCRIPTION:
Similar to definition of STATUS, PROCESS above
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Processing
Alarm, System
Alarm, Process
Alarm, Machine
Fault, Sensor
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
PROCESSING
BIT#:
0