![](https://pdfstore-manualsonline.prod.a.ki/pdfasset/7/ea/7eaa097b-d189-4bb5-bdf6-e2e2808b7a90/7eaa097b-d189-4bb5-bdf6-e2e2808b7a90-bg20.png)
Installation
32 Instruction manual GWV
3
is
Specifications for transition piece and concentric wall flue terminal (C13)
Specifications for transition piece and concentric roof conduit (C33)
Subject Description
Wall flue terminal set:
• 1x wall flue terminal (incl. transition
piece)
• 1x wall plate
• 1x clamping ring
• 2x pipe, 500mm
• 3x bend, 90°
Item No. GWV 120: 0308 241
1
GWV 150: 0308 241
1
GWV 200: 0308 242
1
Construction Concentric
Manufacturer Muelink & Grol
Type GWV 120: M2000 MDV SE 150
GWV 150: M2000 MDV SE 150
GWV 200: M2000 MDV SE 200
Pipe material Construction Parallel
Flue gas
discharge
Thick-walled aluminium with lipped sealing ring
Air supply Thick-walled aluminium with lipped sealing ring
Pipe diameters Flue gas
discharge
GWV 120: Ø 150 mm
GWV 150: Ø 150 mm
GWV 200: Ø 200 mm
Air supply GWV 120: Ø 150 mm
GWV 150: Ø 150 mm
GWV 200: Ø 200 mm
1
No other wall flue terminal is permitted. Use this item number to order the wall conduit set from supplier,
manufacturer or wholesaler.
Subject Description
Roof flue terminal set:
• 1x roof flue terminal (incl. transition
piece)
• 1x adhesive sheet
• 1x clamping ring
• 2x pipe, 1000 mm
• 1x bend, 90°
Item No. GWV 120: 0308 239
1
GWV 150: 0308 239
1
GWV 200: 0308 240
1
Construction Concentric
Manufacturer Muelink & Grol
Type GWV 120: DDV-VR 150/150-150/220
GWV 150: DDV-VR 150/150-150/220
GWV 200: DDV-VR 200/200-200/300
Pipe material Construction Parallel
Flue gas
discharge
Thick-walled aluminium with lipped sealing ring
Air supply Thick-walled aluminium with lipped sealing ring
Pipe diameters Flue gas
discharge
GWV 120: Ø 150 mm
GWV 150: Ø 150 mm
GWV 200: Ø 200 mm
Air supply GWV 120: Ø 150 mm
GWV 150: Ø 150 mm
GWV 200: Ø 200 mm
1
No other wall flue terminal is permitted. Use this item number to order the wall conduit set from supplier,
manufacturer or wholesaler.