FS-8700-86 Carrier DataPort Page 23 of 32
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com
Appendix B.4. How to build a script file that tests a customer log.
The following brief notes are intended for configuration engineers who are expected to be familiar
with the FieldServer.
• Take the hex log file and convert to ASCII using special chars (this is an option of the log file
converter)
• Choose a response line from near the end of the log (most recent). Check the line is complete.
• Place the line inside an INI file. Make the following changes
• Replace [NP] with [FF]
• Replace [SP] with a space
• Replace [NULL] with a space.
• Use the following files as a guide.
Client.csv
Data_Arrays
Data_Array_Name,
Data_Format,
Data_Array_Length
DA_D1_01, Float, 500
Connections
Port , Parity,
Baud,
Data_Bits,
Stop_Bits,
Handshaking,
Protocol, Timeout, Print_storage_locations
P1, None, 9600,
8, 1, None, CarrierDP,
60s, Yes
Nodes
Node_Name,
Node,
Protocol,
Port
Node_A , 1, CarrierDP, P1
Map_Descriptors
Map_Descriptor_Name,
Data_Array_Name,
Data_Array_Offset,
Function,
Node_Name,
Length,
Scan_Interval,
CMD_GP_01, DA_D1_01, 0, Rdbc, Node_A, 202, 5.0s
Server.csv
Data_Arrays
Data_Array_Name,
Data_Format,
Data_Array_Length
TABLE_DISPLAY, Float, 500
Connections
Port , Parity,
Baud,
Data_Bits,
Stop_Bits,
Handshaking,
Protocol,
P1, None, 1200, 8, 1, None, CarrierDP,
Nodes
Node_Name,
Node,
Protocol,
Node_A , 1,