![](https://pdfstore-manualsonline.prod.a.ki/pdfasset/f/c8/fc8419d9-7cd5-4153-ac34-5f4a1bfa5b16/fc8419d9-7cd5-4153-ac34-5f4a1bfa5b16-bg34.png)
CHAPTER 3 Notes on Carrying In and Installing the Product
3.1 Elevator Load Conditions
34
Notes on Carrying In and CHAPTER 3
Installing the Product
This chapter provides notes on carrying in and installing the PRIMEQUEST 2000 series server.
3.1 Elevator Load Conditions
The rack with the device mounted is wider than the average computer. Therefore, to use an elevator to carry
in the rack, the rack may need the side boards or doors removed before loading on the elevator. When using
an elevator to carry in the rack, see the elevator load conditions in “TABLE 3.1 Elevator load conditions” and
confirm that you are properly loading the rack on the elevator.
TABLE 3.1 Elevator load conditions
Elevator
code
Load
capacity
[kg]
(*1)
(*1)
(*1)
(*2)
(*2)
Models
2742/2737/2724/
2642/2624/2616
Models
P-15-C0 1000
2300
2100 Can be loaded
P-17-C0 1150
2300
2100 Can be loaded
P-20-C0 1350
2300
2100 Can be loaded
P-24-C0 1600
2300 1100 2100 Can be loaded
*1 Interior dimensions of the cab [mm]
*2 Door opening dimensions [mm]
3.2 Earthquake Preparedness Measures
The purpose of the earthquake preparedness measures is to prevent the computer from falling and breaking,
and to ensure operator safety as well as quick system recovery. To prevent damage to the computer system
from an earthquake, Fujitsu provides an earthquake countermeasure called "fixed construction." (A fixed
construction prevents the device from falling by fixing it in place.)
The necessity of a fixed construction is determined from the following factors:
- Magnitude of floor vibrations at the installation site
- Whether the floor is a raised floor
- Device structure
Before choosing an earthquake countermeasure and performing the actual work for earthquake
preparedness, consult with Fujitsu's engineering works department.