![](https://pdfstore-manualsonline.prod.a.ki/pdfasset/c/77/c77e852e-c715-41af-bd3f-5fd5117ce0f2/c77e852e-c715-41af-bd3f-5fd5117ce0f2-bg35.png)
3 - 25
MELSEC-F
SPECIFICATIONS3
3 - 25
(Continued from the previous page)
BFM number
Attribute Application Name
Initial value
Decimal
(Hexadecimal)
Flash ROM
save
Reference
section
Decimal
(Hexadecimal)
24320
(5F00
H)
R/W
Mail Function
SMTP server port number
25
(19H)
Section
10.6
24321
(5F01
H)
R/W
SMTP authentication setting
0: No authentication
1: SMTP-AUTH
2: POP before SMTP
Any other value is handled as "0".
0
(0
H)
Section
10.6
24322, 24323
(5F02, 5F03
H)
— System area — — —
24324 to 24355
(5F04 to 5F23
H)
R/W SMTP login ID (64 characters) "\0"
Section
10.6
24356 to 24387
(5F24 to 5F43
H)
R/W SMTP password (64 characters) "\0"
Section
10.6
24388
(5F44
H)
R/W POP3 server port number
110
(6E
H)
Section
10.6
24389 to 24575
(5F45 to 5FFF
H)
— System area — — —
24576 to 31799
(6000 to 7C37
H)
— System area ———
31800
(7C38
H)
R/W
Error information
clear
Error informa-
tion to be
cleared
Designates the error information to be cleared
0000
H :
Clears initial error code (BFM#105)
0001 to 0004
H :
Clears the open error code of
connection 1 to 8 (BFM#124, 134,
144, 154, 164).
Each of the following connection
corresponds.
0001H: Connection 1
0002
H: Connection 2
0003
H: Connection 3
0004
H: Connection 4
0100
H : Clears the error log block area
(BFM#227 to 372) to 0.
0101
H : Clears communication status (status
for each protocol) (BFM#376 to 511)
0103
H :
Clears communication status (E-mail
receive status) (BFM#23353 to 23712)
FFFFH : Clears all of the above
0
(0000H)
—
31801
(7C39
H)
R/W COM.ERR. Off
Designates the function to be cleared
0000
H : [COM.ERR.] LED Off, error code clear
FFFF
H: Error log clear
0
(0000
H)
—
31802
(7C40
H)
R/W
Executing error
clear
Executes error clear
• Write value
0001
H: Executes error clear
• Write value
0002
H: Stored at error clear
The result is stored in BFM#31803
0
(0000
H)
—
31803
(7C41H)
R/W
Result of
execution error
clear
Stores result of execution error clear
0000
H: Normally executed
Other than 0000
H: Error code
0
(0000
H)
—
31804 to 31999
(7C42 to 7CFF
H
)
— System area — — —
32000 to 32639
(7D00 to 7F7F
H
)