5.4 Establishing High and Low Temperature Limits
High and low temperature limits can be separately programmed
for each input configured as temperature. Limits can range from
–20° to +150° Fahrenheit, or from –30° to 65° Celsius.
When temperature limits exceed high or low settings, the Model
1104 will dial out with an alarm message. Default settings are:
10° F for low temperature and 100° F for high temperature.
5.4.1 Programming Temperature Limits for a Selected Input
1. Press SET.
2. Press TEMP LIMITS.
3. From the number keys, press a number (from 1 to 4) that
corresponds to the temperature input being programmed.
The Model 1104 responds: “Enter low temperature limit.”
4. Using the number keys, enter a value for low temperature
limit. The Model 1104 will recite the digits as they are pressed. If
a negative number is required, first press PAUSE, then enter the
number.
5. Press ENTER.
The Model 1104 responds: “Enter high temperature limit.”
6. Using the number keys, enter the value for high temperature
limit. The Model 1104 recites the digits as they are pressed.