Honeywell TR22 TV Mount User Manual


 
INSTALLATION INSTRUCTIONS
62-0267-09
TR21, TR22, TR23, and TR24 Wall
Modules
FEATURES
The TR21, TR22, TR23, and TR24 family of wall modules
include:
Models with setpoint adjustment.
Models with humidity output.
Models with occupied/unoccupied override (bypass)
with LED.
Models with 3-position (auto/0/1) or 5-position
(auto/0/1/2/3 speed) fan switch.
•L
ONWORKS
®
bus jack on all models except the TR21
and TR21-A models.
Locking cover on all models.
Operating range 45° to 99° F (7° to 37° C).
Models (TR22 and TR23) with user-selectable
temperature setpoint dials in Fahrenheit, Celsius, and
Relative (- to +).
PRODUCT DESCRIPTION
The TR21, TR22, TR23, and TR24 are a family of direct-wired
wall modules for use with:
Spyder Unitary Controllers: PUL, PVL
Excel 10 W7750, W7751
a
, W7752, and W7753
controllers
Honeywell Excel 800, 600, 500, 100, and 80 (all fully
programmable) controllers
W7761 Controller
ComfortPoint LON Controllers: CP-UL, CP-VL
All models have a space temperature sensor. Some models
have a temperature dial, setpoint adjustment, L
ONWORKS bus
jack, override (bypass) with LED, and fan switch.
NOTE: Refer to the TR21, TR22, TR23, and TR24 Wall
Modules – Specification Data, form 63-1321, for
specific model features and additional information.
SPECIFICATIONS
Models: For specific model information, see TR21, TR22,
TR23, and TR24 Wall Modules – Specification Data,
form 63-1321.
Environmental Ratings:
Operating Temperature: 45° to 99° F (7° to 37° C).
Shipping Temperature: -40° to 150° F (-40° to 65.5° C).
Accessories: 50007298-001 (pack of 12) medium, cover
plate; 6-7/8 x 5 in. (175 x 127 mm).
Approvals:
CE; UL94 plastic enclosure; FCC Part 15, Class B
Temperature Sensor
TR21, TR22, TR23, and TR24 20K Ohm Nonlinearized
Sensor:
All models are furnished with a 20K Ohm nonlinear NTC
temperature sensor that follows a specific temperature
resistance curve. See Fig. 1 on page 2.
NOTE: The TR21-A wall module model has two (2) 20K
Ohm nonlinear NTC temperature sensors in parallel,
which provide 10K NTC temperature sensing
necessary for averaging.
a
The TR21, TR22, TR23, and TR24 wall modules are not
compatible with W7751A,C,E,G Controllers.