Mitsubishi Electronics FX3S-MT/ES Home Theater Server User Manual


 
41
FX3S Series Programmable Controllers
User's Manual - Hardware Edition
1
Introduction
2
Features and
Part Names
3
Product
Introduction
4
Specifications
5
Version and
Peripheral
Devices
6
System
Configuration
7
Installation
8
Preparation and
Power Supply
Wiring
9
Input Wiring
10
High-Speed
Counters
5 Version Information and Peripheral Equipment Connectability
5.2 Programming Tool Applicability
5.1.2 Version check method
The PLC version number can be checked by reading the last three digits of device D8001/D8101.
5.1.3 Version upgrade history
FX3S Series performed the following upgrade.
5.2 Programming Tool Applicability
5.2.1 Applicable versions of programming tool
1. GX Works2
GX Works2 is applicable to FX3S PLCs from the following versions.
2. FX-30P
FX-30P is applicable to FX3S PLCs from the following version.
5.2.2 In the case of programming tool (version) not applicable
Inapplicable programming tools can be used by selecting an alternative PLC model.
1. Alternative model setting
*1. "FX2N" is selected when the FX-10P(-E) is used.
2. Contents of restrictions
Programming is enabled only in the function range such as instructions, device ranges and program sizes
available in both the FX
3S PLC and the PLC selected as the alternative model.
When the FX-10P(-E) is used, the function range such as instructions, device ranges and program sizes is
limited to that available in both the FX
3S PLC and the FX2N PLC.
Use a programming tool that can select either FX
3G to change parameters, i.e. memory capacity, file
register capacity, etc.
Memory capacity must be set to 4000 steps or less.
Use a programming tool that can select the FX
3G model to program using the built-in USB port.
Version Manufacturer's serial number Contents of version upgrade
Ver. 1.00
133****
(March, 2013)
First product
Ver. 1.10
13X****
(October, 2013)
•FX3S-30M/E-2AD (First product)
Supports connection of following expansion boards:
FX3G-4EX-BD, FX3G-2EYT-BD
Ver. 1.20
14X****
(October, 2014)
Supports connection of display module (FX3S-5DM).
FX3S PLC version Applicable GX Works2 version
Ver. 1.00 Ver. 1.492N or later
FX3S PLC version Applicable FX-30P version
Ver. 1.00 Ver. 1.50 or later
Model to be programmed Model to be set Priority High Low
FX3S PLC
FX3S FX3G
FX1N
*1
FX2N
*1
D8001/D8101
PLC type and
version
2 8 1 0 0
Version information (Example: Ver. 1.00)
PLC type (Example: 28=FX