Trane CNT-PRC002-EN Universal Remote User Manual


 
14 CNT-PRC002-EN
Tracer MP580/581
The specifications in this section apply
to all Tracer MP580/581 models.
Inputs and outputs
Twelve universal inputs
Dry contact binary (including pulse
accumulation), 0–20 mA, 0–10 Vdc,
linear resistance, or thermistor. The
first four inputs can be used directly
with resistance temperature
detectors (RTDs).
Six binary outputs
Tracer MP580: 3 VA per ordered
binary output isolation relay
Tracer MP581: 12 VA at 24 Vac
powered relay contacts
Six analog outputs
0–10 Vdc or 0–20 mA
Static pressure input
Specialized input for a Trane
differential pressure sensor
(5 Vdc, 0–5 in. wc)
Analog-to-digital conversion
Resolution: 12 bits
Digital-to-digital conversion
Resolution: 12 bits
Microprocessor
Motorola MC68332 20 MHz
Memory
RAM: 512 K
ROM: 2 MB Flash
EEPROM: 256 K
Time clock
Included with operator display; crystal
controlled, super-capacitor backed
Battery
Not required—backed by super capacitor
for 7 days under normal operating
conditions; all other programs backed by
non-volatile memory
Agency listings/compliance
CE—Immunity (directive 89/336/EEC)
EN 50090-2-2:1996
CE—Emissions (directive 89/336/EEC)
EN 50090-2-2:1996
EN 61000-3-2:1995
EN 61000-3-3:1995
UL and C-UL listed
Energy management system
UL 916
FCC approved: Part 15, Class A
UL-864-UUKL
Engineered smoke control
Tracer MP581 with
NEMA-1 enclosure
Power requirements
Nominal rating
120/230 Vac; 50/60 Hz; 1 phase
Voltage utilization range
120 Vac nominal: 98–132 Vac
230 Vac nominal: 196–264 Vac
Operating environment
From 32°F to 122°F (0°C to 50°C)
Humidity: 10–90% non-condensing
Storage environment
Temperature
Without display: From –58°F to 203°F
(–50°C to 95°C)
With display: From –13°F to 149°F
(–25°C to 65°C)
Humidity: 10–90% non-condensing
Dimensions
16.5 in. × 14.75 in. × 5.5 in.
(418 mm × 373 mm × 140 mm)
Minimum clearances
12 in. (30 cm) top, bottom, and right
24 in. (60 cm) left
36 in. (90 cm) front
Weight
15 lb (7 kg)
Mounting
Wall-mounted with #10 (5 mm) screws
Frame-mounted
Tracer MP581
Specifications not repeated here are the
same as for the NEMA-1 enclosure.
Power requirements
Nominal rating
24 Vac; 50/60 Hz; 1 phase
Voltage utilization range
24 Vac nominal: 19–30 Vac
Operating environment
From –40°F to 158°F (–40°C to 70°C)
Humidity: 10–90% non-condensing
Dimensions
10.25 in. × 8 in. × 3.5 in.
(260 mm × 203 mm × 89 mm)
Minimum clearances
0.5 in. (1.3 cm) top, right, and front
6 in. (15 cm) left (for I/O wiring)
3 in. (8 cm) bottom (for comm wiring)
Weight
2 lb (1 kg)
Mounting
Requires #8 (4 mm) screws
Factory-installed
Tracer MP580
Specifications not repeated here are the
same as for the NEMA-1 enclosure.
Enclosure
On M-Series air handlers, the Tracer
MP580 controller is mounted in a
galvanized steel enclosure to minimize
costs, facilitate factory mounting, and
match unit construction. On T-Series air
handlers, the Tracer MP580 controller is
mounted in a control panel inside the
unit.
Operator display
On M-Series air handlers, the operator
display can be mounted at the factory or
shipped loose for field installation.
Operator displays are shipped loose for
T-Series air handlers. Door-mounted
operator displays are not available for the
Tracer MP580.
Specifications