1.09 Client Side Map Descriptors
4.1.1. FieldServer Related Map Descriptor Parameters
Column Title Function Legal Values
Map_Descriptor_Na
me
Name of this Map
Descriptor
Up to 32 alphanumeric
characters
Data_Array_Name
Name of Data Array
where data is to be
stored in the
FieldServer
One of the Data Array names
from “Data Array” section
above
Data_Array_Offset
Starting location in
Data Array
0 to maximum specified in
“Data Array” section above
Function
Function of Client Map
Descriptor
RDBC, WRBC, WRBX
4.1.2. Driver Related Map Descriptor Parameters
Column Title Function Legal Values
Node_Name
Name of Node to fetch
data from
One of the node names
specified in “Client Node
Descriptor” above
*Data_Type
(see Note 1
Appendix A.1)
Data type
CIO-WORD, WR-WORD, HR-
WORD, AR-WORD, EM-
WORD
Length
Length of Map
Descriptor
1- 729
Address
Starting address of
read block
0, 1,…100, etc
see Appendix A.1 for details
*Memory_Code
(see Note 1
Appendix A.1)
Memory code for PLC
memory type
B0, B1, B2, B3, 82, 98 and
A0 ---- AC
Command_Name
(see Note 2 section
6.1)
Name of the command
MEMORY AREA READ
MEMORY AREA WRITE
RUN-STOP
CLOCK READ
CLOCK WRITE
CYCLE TIME READ
CPU UNIT STATUS READ
*MRC
(see Note 2
Appendix A.1)
Main Request Code 1,4,6,7
*SRC
(see Note 2
Appendix A.1)
Sub Request Code 1,2,20