A SERVICE OF

logo

FS-8704-16 Omron FINS Manual Page 19 of 37
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com
5.1.4. Map Descriptor Example 2: IO Write
This Map Descriptor makes the memory area writable which was made readable by the previous Map Descriptor.
Thus memory area can be made read only, write only or read and write enabled.
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name Address Length Data_Type Command_Name Unit_number
SRV_CIOw, DA_CIO, 0, SERVER, PLC1, 0, 6143, CIO-WORD MEMORY AREA WRITE 0
5.1.5. Map Descriptor Example 3: Clock Read:
This Map Descriptor enables the Driver to serve the client with a Clock read request. See Appendix B.1for further
information
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name Length Command_Name Unit_Number
SRV_CLKr, DA_CLKr, 0, SERVER, PLC1, 7, CLOCK READ 0s
5.1.6. Map Descriptor Example 4: Clock Write:
This Map Descriptor enables the Driver to update Clock information when the Client makes a Clock Write request. See
section Appendix B.1 for further information.
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_name Length Command_Name Unit_Number
SRV_CLKr, DA_CLKr, 0, SERVER, PLC1, 7, CLOCK WRITE 0
5.1.7. Map Descriptor Example 5: CPU Cycle Times:
This Map Descriptor enables the Driver to serve Clients with CPU cycle time information upon request. See Appendix
B.1 for further information.
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name Length Command_Name Unit_Number
SRV_CYCT, DA_CYCT, 0, SERVER, PLC1, 7, CLOCK READ 0