A SERVICE OF

logo

FS-8704-16 Omron FINS Manual Page 1 of 37
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com
1. Omron FINS Description
The Ethernet Omron FINS driver allows the FieldServer to transfer data to and from
devices over Ethernet using Omron FINS protocol. The FieldServer can emulate either
a Server or Client.
FINS is an Omron protocol which can be used by a PLC program to transfer data and
perform other services with a remote PLC connected on an Ethernet Network. It can
also be used by remote devices such as PC’s and FieldServer’s to transfer data and
perform other services.
The protocol uses the Ethernet protocol called UDP to carry the FINS messages back
and forth. The UDP protocol is not connection based and reliability is achieved by using
confirmation messages.
This Ethernet Driver can be used to transfer data to and from the Nodes supporting
FINS communications.
Max Nodes Supported
FieldServer Mode Nodes Comments
Client 126
Omron limit the set of permitted nodes to 126. They are
numbered 1 to 126 corresponding to the last byte of the
remote node IP address.
Server 20
The FieldServer can emulate a maximum of 20 Omron
FINS servers.