A SERVICE OF

logo

1-30 SPARC Enterprise M8000/M9000 Servers Site Planning Guide • April 2008
FIGURE 1-24 SPARC Enterprise M9000 Server (Base Cabinet + Expansion Cabinet) + Power Cabinet
Footprint
1.2.2.4 Ceiling Height
The minimum ceiling height for the SPARC Enterprise M8000/M9000 server is 2.3m
(7.5 feet), measured from the true floor or a raised floor, whichever is higher. The
space above the server and its surroundings must not restrict the movement of
cooling air between the air conditioner and the server.
The space above the server and its surroundings must not restrict the following:
The movement of cooling air between the air conditioner and the bottom of the
server
The movement of the hot air coming out of the top of the server
Unit: mm (inch)
Front
Opening for air conditioning from the
bottom
(The opening should be in the shaded
free-access area. It cannot be shared
with the opening for cables out.)
Caster
Feet