Carrier 50TCA04-A07 DVD Player User Manual


 
35
and D. See Fig. 59 for the corresponding temperature
change over values.
C06034
Fig. 58 -- EconoMi$er IV Controller Potentiomete r
and LED Locations
LED ON
LED ON
LED ON
LED ON
LED OFF
19
18
LED OFF
LED OFF
LED OFF
17
16
15
14
13
12
11
10
9
40
45
50
55
60
65
70
75
80
85
90
95
100
DEGREES FAHRENHEIT
mA
D
C
B
A
C06035
Fig. 59 -- Outside Air Temperature Changeover
Setpoints
0
5
10
15
20
25
30
0.13 0.20 0.22 0.25 0.30 0.35 0.40 0.45 0.50
STATIC PRESSURE (in. wg)
FLOW IN CUBIC FEET PER MINUTE (cfm)
C06031
Fig. 60 -- Outdoor--Air Damper Leakage
Differential Dry Bulb Control
For differential dry bulb control the standard outdoor dry
bulb sensor is used in conjuncti on with an additional
accessory dry bulb sensor (part number
CRTEMPSN002A00). The accessory sensor must be
mounted in the return airstream. (See Fig. 61.) Wiring i s
provided in the EconoMi$er IV wiring harness. (See Fig.
52.)
ECONOMI$ERIV
ECONOMI$ERIV
CONTROLLER
GROMMET
RETURN AIR
SENSOR
RETURN DUCT
(FIELD-PROVIDED)
C07085
Fig. 61 -- Return Air Temperature or Enthalpy Sensor
Mounting Location
In this mode of operation, the outdoor-air temperature is
compared to the return-air temperature and the lower
temperature airstream is used for cooling. When using this
mode of changeover control, turn the ent halpy setpoint
potentiometer fully clockwise to the D setting. (See Fig.
58.)
Outdoor Enthalpy Changeover
For enthalpy control, accessory enthalpy sensor (part
number HH57AC078) is required. Replace the standard
outdoor dry bulb temperature sensor with the accessory
entha lpy sensor in the same mounting location. (See 56.)
When the outdoor air enthalpy rises above the outdoor
entha lpy changeover setpoint, the outdoor-air damper
moves to its minimum position. The outdoor enthalpy
change over setpoint is set with the outdoor enthalpy
setpoint potentiom eter on the EconoMi$er IV controller.
The setpoints are A, B, C, and D. (See Fig. 62.) The
factory-installed 620-ohm jumper must be in place across
terminals S
R
and SR+ on the EconoMi$er IV controller.
(See Fig. 52 and 63.)