Mitsubishi Electronics A1SJ61BT11 Home Theater Server User Manual


 
9 - 9
9 COMMUNICATION BETWEEN THE MASTER STATION AND THE
REMOTE I/O STATION
MELSEC-QnA
SM400
For communication
w
ith AJ65BTC1-32T
(station No.4)
N0MCR
K4M200 K5TO H0004 H0164
Write to the remote output
(RY)
X60
M232
X7F
M263
When X60 to X7F of the
master station AX42 is
turned on, output (Y00 to
Y1F) of AJ65BTC1-32T
is turned on.
to
For communication
w
ith AJ65BTB1-16DT
(station No.5)
M128
YC0
M135
YC7
When input (X00 to X07)
of AJ65BTB1-16DT is
turned on, YC0 to YC7
of the master station
AY42 is turned on.
to
X80
M272
X87
M279
When X80 to X87 of the
master station AY42 is
turned on, output (Y08 to
Y0F) of AJ65BTB1-16DT
is turned on.
to