Mitsubishi Electronics A1SJ61BT11 Home Theater Server User Manual


 
15 - 16
MELSEC-QnA
15 FUNCTIONS (FUNCTION VERSION B OR LATER)
(2) Link special registers (SW)
The link special registers (SW) relating to the cut-off station specification function
are as follows. The figures in parentheses in the number column indicate buffer
memory address.
Table 15.10 List of link special registers relating to temporary error invalid station specifying function
Availability
(
: available,
: not available)
Number Name Description
Master station Local station
SW0003
(603
H)
Multiple temporary error
invalid station specification
Selects whether to specify multiple temporary error invalid stations.
00 : Specifies multiple stations as indicated in SW0004 to
SW0007.
01 to 64 : Specifies a single station from 1 to 64.
Specifies the station number used as the temporary invalid station.
SW0004
(604
H)
·
SW0005
(605
H)
·
SW0006
(606
H)
·
SW0007
(607
H)
Temporary error invalid
station specification
1
Specifies the temporary error invalid station.
0: Not specified as a temporary error invalid station.
1: Specified as a temporary error invalid station.
1SW0004
b0
1 to 64 in the table indicate station numbers.
2
b1
3
b2
4
b3
to
to
13
b12
14
b13
15
b14
16
b15
17SW0005 181920
to
29303132
33
SW0006
34
35
36to
45
46
4748
49SW0007 505152
to
61626364
SW0049
(649
H)
Temporary error invalid
station request result
Stores the results of execution of the temporary error invalid station
request instruction by SB0004.
0 : Normal
Other than 0 : Store error code (See Section 13.3)
SW004B
(64B
H)
Temporary error invalid
station cancelling request
result
Stores the results of execution of the temporary error invalid station
cancelling request instruction by SB0005.
0 : Normal
Other than 0 : Store error code (See Section 13.3)
SW007C
(67C
H)
·
SW007D
(67D
H)
·
SW007E
(67E
H)
·
SW007F
(67F
H)
Temporary error invalid
station specifying status
1
Stores the temporary error invalid station specifying status.
0: Other than temporary error invalid station
1: Temporary error invalid station
1
S
W007C
b0
1 to 64 in the table indicate station numbers.
2
b1
3
b2
4
b3
to
to
13
b12
14
b13
15
b14
16
b15
17
S
W007D
18
19
20
to
29
30
3132
33343536to45464748
49505152
to
61626364
SW007E
SW007F
1 Turns on only the bit for the head station number.
POINT
(1) When both a temporary error invalid request and a cut-off cancelling request are made, the
cut-off cancelling request will be given a priority.
(2) For a station that occupies multiple stations, only the head station number becomes valid.