Mitsubishi Electronics A1SJ61QBT11 Home Theater Server User Manual


 
10 - 9
10 COMMUNICATION BETWEEN THE MASTER STATION AND THE
REMOTE DEVICE STATION
MELSEC-QnA
X0040 X004F
P10CALL
Read the data link status
(SW0080) from the remote
device station
AJ65BT-64AD data link is
proceeding
K1M401 K1FROM H0004 H0680
M24 (Initial data processing request flag: RX18)
H0202 D200MOV
Averaging process specification
(CH2 average time)
H0001 D205MOV
H0003 D206MOV
Data type (-2048 to 2047)
A/D conversion enable/disable
specification (CH1, CH2
conversion permission)
FEND
Initial settings
X0041
M401
AJ65BT-64AD data link is
in error
M401
YA0
P20CALL
AJ65BT-64DAV data link is
in proceeding
M403
AJ65BT-64DAV data link is
in error
M403
YA1
SM400
Read AJ65BT-64AD remote
input (RX)
K4M0 K2FROM H0004 H00E0
P10
Communication
program with
A
J65BT-64AD
K60 D202MOV
CH2 Average time,
number of times (60ms)
D200 K1TO H0004 H01E0
D205 K2TO H0004 H01E5
D202 K1TO H0004 H01E2
M124SET
Initial data processing
complete (RY18)
M125SET
Initial data setting
reguest (RY19)
M124RST
M125RST
M25 (Initial data setting complete flag : RX19)
M24