Panasonic FP0 Series Universal Remote User Manual


 
Item Description
Rated operating voltage 24 VDC
Operating voltage range 21.6 to 26.4 VDC
Allowable no voltage time
10 points, 14 points type
5ms (at 21.6 V), 10ms (at 24 V)
16 points, 32 points, S-LINK type
10ms (at 21.6 V / 24 V)
Ambient temperature 0°C to +55°C
Storage temperature -20°C to +70°C
Ambient humidity 30 to 85% RH (Non-condensing)
Storage humidity 30 to 85% RH (Non-condensing)
Breakdown voltage
Between input/output terminals and power/ground terminals: 500VAC for 1 minute (for the relay output type, 1500VAC for 1 minute)
Between input terminals and output terminals: 500VAC for 1 minute (for the relay output type, 1500VAC for 1 minute)
Insulation resistance
Between input/output terminals and power/ground terminals: Over 100 M (using a 500VDC megger)
Between input terminals and output terminals: Over 100M (using a 500VDC megger)
Vibration resistance 10 to 55Hz, 1 sweep/min., double amplitude of 0.75mm, 10min. on 3 axes
Shock resistance
98m/s
2
or more, 4 times on 3 axes
Noise immunity 1,000 V(p-p) with pulse widths 50ns and 1ms (using a noise simulator)
Operating condition Free from corrosive gasses and excessive dust
Type of control unit
C10 series C14 series C16 series C32 series
S-LINK type
T32 series
Programming method / Control method Relay symbol/Cyclic operation
Number of
I/O points
No expansion
(control unit only)
Total: 10
Total: 14
Total: 16
Total: 32
Total: 32
W/expansion 1
*Same type of control and expansion units
Max. 58 Max. 62 Max. 112 Max. 128
Expansion section:
max.96 points
Max. 128
W/expansion 2
*Mix type of relay and transistor units
Max. 106 Max. 110 Max. 112 Max. 128 Max. 128
Program memory EEPROM (No back-up battery required)
Program capacity 2.7K steps 5K steps 10K steps
Kinds of
instruction
Basic 83
High-level 115
Operation speed (central value/step) 0.9µs (Basic instruction)
Memory for
execution
Relay
Intermal relay (R)
1,008 points
Timer/Counter (T/C)
144 points
Memory
area
Data register (DT)
1,660 words 6,144 words 16,384 words
Index register(IX,IY)
2 words
Master control relay (MCR) 32 points
Number of labels (JMP and LOOP) 64 labels 255 labels
Differential points Unlimited number of points
Number of step ladder 128 stages 704 stages
Number of subroutines 16 subroutines 100 subroutines
Special
functions
High speed counter
1 phase/4 points (10kHz in total) or 2 phases / 2 points (2kHz in total)*
Not available
Pulse output Not available
2 points (10 kHz* in total),enable to control 2
channels individually*
Not available
PWM output Not available 0.15Hz to 1kHz Not available
Pulse catch input/interrupt input
6 points(with high speed counter) Not available
Interrupt program 7 programs (external 6 points, internal 1 point)
Periodical interrupt 0.5ms to 30s
Constant scan Available
RS232C port
One RS232C port is mounted on each of the models FP0- C10CR, C14CR,C16CT, C16CP, C32CT, C32CP, T32CT, T32CP and SL1 type (3P terminal block)
Transmission speed (Baud rate): 300 to 19200bits/s , 3m Communication method: half duplex
Transmission distance: 3m
Maintenance
Memory
back up
Stored program and system register in EEPROM
Operation
memory
Stored fixed area in EEPROM
Counter: 4 points
Internal relay: 32 points
Data register: 8 words
Counter: 16 points
Internal relay: 128 points
Date register: 32 words
Backup is provided by
secondary battery. The
holding range for the
timers, counters, internal
relays, and data regis-
ters are specified with
the programming tool.
Self-diagnosis functions Watchdog timer, program syntax checking, etc.
Clock/calender function Not available Available
Other functions Runtime editing, password setting
* For the limitations while operating units, see the manual.
Stored fixed area in EEPROM
Total:128
(Input: 6, Output: 4) (Input: 8, Output: 6) (Input: 8, Output: 8) (Input: 16, Output: 16) (Input: 64, Output: 64) (Input: 16, Output: 16)
Program and system register
(Relay output type only) (Relay output type only)
(Transistor output type only) (Transistor output type only) (Transistor output type only)
Available (same as
32 points series)
1 program (internal 1 point)
Available (same as
32 points series)
FP0 Series
Specification tables
17
FP0 Specifications