Teledyne T200U-NOy TV Converter Box User Manual


 
Model T200U-NOy Option Manual Addendum
34 07303C DCN6646
SECONDARY MENU (The fixed characteristics of the system).
PRESS DISPLAY ACTION
SEL hold until
p-n1
SET TO 0 – REVERSE ACTION
SEL hold until
p-n2
SET TO 2 = TYPE J THERMOCOUPLE
SEL
p-dF DIGITAL FILTER
SET TO 5
SEL
P-SL LOWER LIMIT
SET TO -40 (-40ºC)
SEL
P-SU UPPER LIMIT
SET TO 350 (350ºC)
SEL
P-AH ALARM
SET TO 0
SEL
P-An HYTERESIS
SET TO 5
SEL
P-dP PROG DECIMAL
SET TO 0
SEL
PVOF PROCESS OFFSET
LEAVE AT 0
SEL
SVOF SET POINT OFFS
LEAVE AT 0
SEL
P-F
SET TO 0 (0 =
o
C, 1 =
o
F)
SEL
P-n1
ALREADY CONFIGURED
SEL hold until RETURNS TO MAIN MENU
SEL
PV/SV
SET DISPLAY TO 315 C
SEL hold until
P PROP BAND
ALREADY CONFIGURED
SEL
SCROLL TO A7
SET TO 1 (AUTOTUNE )