General Reference Data
Data
Isolation
(Functional)
AC Power :
is electrically isolated from all other inputs and outputs to withstand a HIPOT potential of
1900Vdc for 2 seconds per Annex K of EN61010-1.
Analog Inputs and Outputs:
are isolated from each other and all other circuits at 850Vdc for 2 seconds.
Digital Input and Digital Output:
are isolated from all other circuits at 850Vdc for 2 seconds.
Relay Contacts:
with a working of 115/230 Vac, isolated from each other and all other circuits at
345 Vdc for 2 seconds.
Surge Withstand
Capability (SWC)
Immunity:
ANSI/IEEE C37.90.1, Surge Withstand Capability (SWC) (Formerly IEEE 472) Mains power
input and relay contact outputs: 2.5 kV, Common Mode and Differential Mode. All other circuits: 1.0 kV,
Common Mode and Differential Mode.
Radio Frequency
Interference (RFI)
Immunity
: No effect on performance from a 5 W walkie-talkie operated at 27, 151 or 450 MHz, one
meter from the controller.
Model Number Interpretation
Output #1
C = Current 4 – 20mA without Alarms
K = Current 4 – 20mA with Alarm 1
E = Relay, Electromechanical – 5AMP with Alarm 1
A = Relay, Solid State AC – 1AMP with Alarm 1
T = Open Collector Output – 20mA with 1 Alarm
DC3 0 0
Output #2 or Alarm #2
O = None
E = Relay, Electromechanical – 5AMP (SPDT)
A = Relay, Solid State AC – 1AMP (SPST)
T = Open Collector Output – 20mA
External Interface
O – – = None
1 – – = RS422/485
2 – – = Auxiliary Output
4 – – = DMCS
Software Options
– O – = None
A – = Accutune
B – = Setpoint Program and Accutune
Digital Inputs
– – O = None
– – 3 = Digital Inputs (2)
Table 1 Table 2 Table 3 Table 4 Table 5Key Number
0
Options
0 – – – =
1 – – – =
B – – – =
T – – – =
C – – – =
D – – – =
– 0– – =
– A – – =
– F – – =
– – 0– =
– – T – =
– – – 0 =
– – – D =
90-264Vac Power
24Vac/dc Power
Blue Bezel with
90-264Vac Power
Tan Bezel with
90-264 Vac Power
Blue Bezel with
24Vac/dc Power
Tan Bezel with
24Vac/dc Power
None
Approvals -
CSA,FM,UL
Approvals - FM,
CSA
None
Customer I.D. Tag
None
DIN Cutout
Adapter
PV Input
1 – =
2 =
3 =
T/C, RTD, mV, 1–5V
T/C, RTD, mV, 1–5V,
4–20mA
T/C, RTD, mV, 1–5V,
4–20mA,0–10V
Optional Input
– 0 =
– 1 =
– 2 =
None
4–20mA or 1–5V
Slidewire Input for Position
Proportional or 3 Position
Step with motor position
indication
22603
Figure 4 - Model Number Interpretation