51-52-03-27
Page 8
Specifications, continued
Environmental and Operating Conditions
Parameter Reference Rated Operative Limits Transportation and Storage
Ambient Temperature
25 ± 3°C
77 ± 5°F
0 to 55°C
32 to 131°F
0 to 60°C
32 to 140°F
–40 to 66°C
–40 to 151°F
Relative Humidity
10 to 55* 10 to 90* 5 to 90* 5 to 95*
Vibration
Frequency (Hz)
Acceleration (g)
0
0
0 to 70
0.4
0 to 200
0.6
0 to 200
0.5
Mechanical Shock
Acceleration (g)
Duration (ms))
0
0
1
30
5
30
20
30
Voltage (Vdc, Vac)
+24 ±1 20 to 27 20 to 27 - -
Voltage (Vac)
90 to 264 Vac
(CSA models rated to 250V max.)
120 ±1
240 ±2
90 to 264 90 to 264 - -
- -
Frequency (Hz)
(For Vac)
50 ±0.2
60 ±0.2
49 to 51
59 to 61
48 to 52
58 to 62
- -
- -
* The maximum rating only applies up to 40°C (104°F). For higher temperatures, the RH specification is derated to maintain constant moisture content.
Table 1—Input Actuations
Range
PV Input °F °C
Thermocouples
(Per ITS-90)
B
E
E (low)
J
J (low)
K
K (low)
NiNiMoly (NNM68)
NiNiMoly (low)
NiMo-NiCo(NNM90)
NiMo-NiCo (low)
Nicrosil Nisil (NIC)
R
S
T
T (low)
W5W26
W5W26 (low)
0 to 3300
–454 to 1832
–200 to 1100
0 to 1600
20 to 770
0 to 2400
–20 to 1000
32 to 2500
32 to 1260
32 to 2500
32 to 1260
0 to 2372
0 to 3100
0 to 3100
–300 to 700
–200 to 500
0 to 4200
0 to 2240
–18 to 1816
–270 to 1000
–129 to 593
–18 to 871
–7 to 410
–18 to 1316
–29 to 538
0 to 1371
0 to 682
0 to 1371
0 to 682
–18 to 1300
–18 to 1704
–18 to 1704
–184 to 371
–129 to 260
–18 to 2315
–18 to 1227
Honeywell Radiamatic
Type RH
Type RI
0 to 3400
0 to 9999 max.*
–18 to 1871
–18 to 9999 max.*
*User enters the range manually per RI type and application.
Range
PV Input °F °C
RTD
IEC Alpha = 0.00385
100 ohms
100 ohms (low)
200 ohms
500 ohms
–300 to 1200
–300 to 300
–300 to 1200
–300 to 1200
–184 to 649
–184 to 149
–184 to 649
–184 to 649
Linear
Milliamps
Millivolts
Volts
4 to 20 mA
0 to 20 mA
0 to 10 mV
0 to 100 mV
1to 5 V
0to 5 V
0 to 10V