5 - 10
MELSEC-A
5 PROGRAMMING
(2) Program example for initial data changing
Setting of
network
parameters
Setting of
automatic
refresh
parameters
Synchronization
mode invalid
Dedicated instruction
(RLPA)
Starting I/O number of
master module
Parameter storage
starting device
Device which turns on 1
scan at completion
Reads parameter status
at abnormal completion.
Sets RX starting number.
Sets "X".
Sets X100.
Sets RY starting number.
AJ65SBT-64AD station
information (remote
device station, 1 station
occupied, station No. 1)
Number of connected
modules:1
Sets 32 points.
Sets "Y".
Sets Y100.
Sets 32 points.
Sets RW starting number
.
Sets "D".
Sets D200.
Sets 260 points.
Sets SB starting number.
Sets "B".
Sets B0.
Sets 512 points.
Sets SW starting number
.
Sets W0.
Sets "W".