7. Specifications
Table 7.1: General specifications
Item Specifications
Ambient temperature
range
0 to +55
°
C during operation, -20 to +70
°
C during storage
Ambient humidity 35 to 85 % RH during operation (Dew condensation shall not be allowed.)
Vibration resistance
In conformance to JIS C0040
Frequency 10 to 57 Hz, half amplitude 0.075 mm, 57 to 150 Hz, acceleration 9.8
m/s
2
, 10 times in each of X, Y and Z directions (80 times in total)
(For product installed with DIN rail: Frequency 10 to 57 Hz, half amplitude 0.035
mm, 57 to 150 Hz, acceleration 4.9 m/s
2
)
Impact resistance
In conformance to JIS C0041
147 m/s
2
for 11 ms, 3 times in each of X, Y and Z directions with half-sine pulses
Noise resistance
By noise simulator of noise voltage 1,000 Vp-p, noise width 1
µ
s and frequency
30 to 100 Hz
Withstand voltage
500 V AC for 1 min
(between analog input terminal and each terminal of PLC main unit)
Insulation resistance
In conformance to JEM-1021
5 M
or more by 500 V DC Megger (between all terminals as a whole and case)
Operating
atmosphere
Corrosive gas and much dusts shall not be detected.