NOTE: If using a refillable tank, install the tank upside down, and connect the fill
hose to the vapor valve.
4. Press the START key, and the tank automatically refills. The unit stops when
a sufficient amount of refrigerant has been transferred to the internal tank, or
if the source tank is empty. Press the STOP key to pause the process. Press
STOP again to exit, or START to resume.
5. When the fill process is complete, press STOP to exit.
VACUUM OIL TIME
This function displays how long the vacuum pump has run since the last oil
change.
1. Press the MENU key. Use the arrow keys to select VACUUM OIL TIME, and
press START to begin.
2. The display reads: OIL TIME = XX:XX This shows how long the pump has
run since the last oil change. The time resets to zero after a VACUUM PUMP
OIL CHANGE. See page 20 of this manual for details.
3. Press STOP to exit.
FILTER CAPACITY
This function is used to show the operator how many pounds or kilograms of
refrigerant have been recovered since the last filter change.
1. Press the MENU key. Use the arrow keys to select FILTER CAPACITY, and
press START to begin.
2. The display reads: FILTERED= XXXlbs(kg). This shows how much
refrigerant has passed through the filter. The amount filtered resets to zero
after a FILTER CHANGE. See page 19 of this manual for details.
3. Press STOP to exit.
SELECT PROMPT (BASIC/ADVANCED)
Use the BASIC PROMPT option to receive step-by-step, on-screen prompting
through any procedure. Use ADVANCED PROMPT once you know the procedure
and no longer need the step-by-step routine.
1. Press the MENU key. Use the arrow keys to choose SELECT PROMPT, and
press START to begin.
2. Toggle between BASIC/ADVANCED using the ARROW keys.
3. Press START to save the current choice and exit.
NOTE: This manual is written for the BASIC PROMPT option.
Operating Guidelines