Fujitsu M8000 Home Theater Server User Manual


 
2-6 SPARC Enterprise M8000/M9000 Servers Site Planning Guide September 2007
Power Cabinet
SPARC
Enterprise
M9000 Server
(base cabinet +
expansion
cabinet)
1
200 to
240
VAC
±10%
Single 50/60
+2%, -4%
42.6
5
44.8
5
0.9 or
higher
100 or
less
6
4.1 or
less
6
30
7
Rack-
mountable
Dual Power
Feed
(for SPARC
Enterprise
M8000 Server)
200 to
240
VAC
±10%
10.5
2
11.0
2
0.9 or
higher
100 or
less
6
4.1 or
less
6
30
7
1 This value represents when power feed is through the Power Cabinet alone.
2 This value is reached when four CMUs and four IOUs are installed.
3 The 100V power supply is used only for the FST, and this specification applies only to use in Japan.
4 This value is reached when eight CMUs and eight IOUs are installed
5 This value is reached when 16 CMUs and 16 IOUs are installed.
6 This value represents the current for each cable.
7 This value represents the capacity of a system main line switch for each power supply of the single-phase power supplies.
TABLE 2-4 Specifications (Single-Phase Power Requirements) (2 of 2)
Name
Power supply
Power
consumption
[kW]
Apparent
power
[kVA]
Power
factor
Rush
current
[A0-p]
Leak
current
[mA]
Circuit
breaker
capacity
[A]
Voltage
[V] Phase
Frequency
[Hz]