6) Program example
(1) Distinction program of A/D conversion value(Analog input range: DC420 , 0~10VDC)
(a) Program explanation
When digital value of channel 0 is the same or more than 2000 and the same or less than 3000, P090 is on.
When digital value of channel 1 is the same or more than 2000 and the same or less than 3000, P091 is on.
When digital value of channel 2 is the same or more than 2000 and the same or less than 3000, P092 is on.
When digital value of channel 3 is the same or more than 2000 and the same or less than 3000, P093 is on.
(b) System configuration
Analog input
channel “0”, “1” : Voltage input (010VDC)
channel “2”, “3” : Current input (DC 420 )
Parameter setting
System configuration
Main Unit A/D conversion module Expansion module
I/O allocation
Main unit input : P000 ~ P03F
Main unit output : P050 ~ P07F
Expansion module input : P080 ~ P08F
Expansion module output : P090 ~ P09F